iO4R relay expander for the GATOR gate controller – installation and setup manual

Installation and setup manual for the Trikdis iO4R relay expander: connection to the GATOR gate controller, monitoring and bypassing the safety sensors, gate cycle counting and maintenance, the Protegus 2 app.

  • 20 min read
iO4R relay expander for the GATOR gate controller – installation and setup manual

1. Overview

The iO4R (also called IO4R, iO-4R) is the Trikdis relay expander for the GATOR gate controllers: it adds four inputs and four relay outputs to the gate controller, to which it connects over the RS485 bus. Its main job is gate monitoring: the safety sensors of the gate automation (for example the photocells) are connected to the gate automation through the iO4R, so their state is visible in the Protegus 2 app, and a failed sensor can be bypassed remotely by an authorized person, temporarily, until the service technician arrives. Meanwhile Protegus 2 counts the gate's full open–close cycles and signals when maintenance is due.

The iO4R relay expander board with numbered markers
Figure 1. The iO4R expander board.
  • 1 +DC, −DC – power supply, 10–26 V DC
  • 2 A, B (marked “485” on the board) – RS485 bus to the gate controller
  • 3 inputs 1 and 2 with the C (common) terminals
  • 4 inputs 3 and 4 with the C (common) terminal
  • 5 TROUBLE indicator
  • 6 POWER indicator
  • 7 jumper block marked “8K2” (JP1, 1–4)
  • 8 the output terminals of the four relays: 1NO 1C 1NC … 4NO 4C 4NC

1.1 What it is for, how it works

It is made for installers: some of the critical faults can be solved remotely with the iO4R, so an unnecessary site visit is avoided. Typical cases:

  • The gate does not close because a safety sensor has failed or is obstructed: the installer bypasses the input remotely, and the gate works again immediately – there is no need to rush to the site, and the gate does not stand idle either.
  • Monitored inputs: safety sensors, limit switches or external trigger signals can be connected to the inputs, and their state is visible in real time.
  • Remote relay control: with the four relay outputs you can start the gate remotely, reset a state, or switch another external device.
  • Maintenance by cycle count: Protegus 2 counts the full open–close cycles and signals when the set maintenance value has been reached.
  • Expansion: with four inputs and four outputs it gives the GATOR system more control and automation options; it can be used both in a new installation and to expand an existing system.

How does it work? The iO4R works on the RS485 bus of the gate controller, as the GATOR system's own expansion: input changes and remote commands pass between the two devices without delay. The output of the gate automation's safety sensor goes to one of the iO4R inputs, and the output of the relay belonging to it goes to the safety input of the gate automation. Each input has the relay output with the same number:

Input Relay output
Input 1 Output 1 (1NO / 1C / 1NC)
Input 2 Output 2 (2NO / 2C / 2NC)
Input 3 Output 3 (3NO / 3C / 3NC)
Input 4 Output 4 (4NO / 4C / 4NC)

You set up the system in the Protegus 2 app, in the Advanced Gator Monitoring mode that can be selected when the gate controller is added (chapter 4). The other settings of the gate controller are described in the GV17 GATOR manual and the WP17 GATOR WiFi manual – this manual is to be used alongside them.

Trikdis IO4R (IO-4R) – GATOR I/O Expander Module (4 Inputs / 4 Relays)Trikdis IO4R (IO-4R) – GATOR I/O Expander Module (4 Inputs / 4 Relays)

1.2 Compatible gate controllers

The iO4R is made specifically for the GATOR gate controllers and connects to them over the RS485 bus. It works with two gate controllers:

Gate controller Also called Manual
GV17 GATOR – cellular (4G) gate controller GATOR LTE GV17 manual
WP17 GATOR WiFi – Wi-Fi gate controller GATOR WiFi WP17 manual

One iO4R can be connected to one gate controller.

Trikdis GV17 - GATOR smart 4G GSM / IP gate controllerTrikdis GV17 - GATOR smart 4G GSM / IP gate controller Trikdis WP17 Smart WiFi controllerTrikdis WP17 Smart WiFi controller

1.3 Technical data

Parameter Value
Supply voltage 10–26 V DC
Current consumption max. 100 mA (at 12 V DC)
Connection to the gate controller RS485 bus
Inputs 4
Input type EOL (supervised with an end-of-line resistor), nominal resistance 8.2 kΩ
Input voltage from 0 V up to the supply voltage
Outputs 4 relays with NC/NO contacts
Output resistance an 8.2 kΩ resistor can be switched onto the NO terminal – for systems that require a supervised output
Output voltage 0–125 V
Output current max. 1 A (at 30 V DC)
Operating environment −10 … +55 °C, max. 80% relative humidity (at +20 °C)

No dimensions are given; the module is compact and can also be fitted inside the gate automation housing.

1.4 Terminals and indicators

Terminal Function
+DC, −DC power supply, 10–26 V DC
A, B (“485” on the board, RS485A, RS485B on the drawing) RS485 bus: to the A RS485 and B RS485 terminals of the gate controller
1, 2, 3, 4 the four inputs; the sensor contact goes between the input and the C terminal next to it
C common terminal of the inputs
1NO 1C 1NC … 4NO 4C 4NC the contacts of the four relays: NO – normally open, C – common, NC – normally closed

Two indicators on the board help with troubleshooting:

  • POWER – the state of the supply voltage: normal or low supply voltage;
  • TROUBLE – the RS485 communication with the gate controller has been lost.

Indicators also show the state changes of the inputs and outputs, so the installer can quickly see what is happening in the system. This manual does not detail the blink patterns.

Next to the relays, the board has a four-position jumper block labelled “8K2” (JP1, 1–4). An 8.2 kΩ resistor can be switched onto the NO terminal of the relay outputs: with the jumper fitted the resistor is connected, with the jumper removed it is not. Which one is needed depends on the gate automation.

2. Preparation

Before you start, you will need the following:

  1. The GV17 GATOR or WP17 GATOR WiFi gate controller that you are setting up now. It must be powered off while you are wiring.
  2. The iO4R serial number – Protegus 2 asks for it during setup.
  3. A Protegus 2 company or installer account, and the gate controller's IMEI number / unique ID (Unique ID) – it can also be found as a QR code on the gate controller's sticker.
  4. A gate status sensor (for example the gate's limit switch or the status output of the gate automation) connected to the gate status input of the gate controller: in iO4R monitoring this is the 3 I/O input (section 3.4).
  5. The gate's safety sensors (for example photocells) wired through the iO4R – if you want to monitor them in Protegus 2 or bypass them when needed.
Protegus 2
Protegus 2 at Play store
Protegus 2 at App store
Protegus 2 app in any browser

3. Wiring

Warining!

It is forbidden to perform wiring on a device under voltage. Before starting the work, disconnect power (including backup batteries).

The iO4R connects to the RS485 bus and the power supply of the gate controller, and the safety sensors are connected to the gate automation through it. The complete wiring is shown in the drawing below.

Wiring diagram of the iO4R with the GATOR gate controller, the power supply and the gate automation, with numbered markers
Figure 2. Wiring the iO4R to the GATOR gate controller and the control unit of the gate automation (“Gate automatic”). The input of the power supply (“Power supply”) is ~230 V; its +12 V and 0 V outputs go to the AC/+DC and AC/−DC terminals of the GATOR and to the +DC and −DC terminals of the iO4R. RS485 bus: the A RS485 and B RS485 terminals of the GATOR go to the RS485A and RS485B terminals of the iO4R.
  • 1 the output of the gate automation's safety sensor is wired to the input of the iO4R module: to terminals 1 and C (“The output of the gate automation safety sensor are wired to the input of the iO4R module”)
  • 2 the output of the iO4R module is wired to the safety input of the gate automation: 1C to COM, 1NC to IN (“The output of the iO4R module are wired to the safety input of the gate automation”)
  • 3 the gate status signal (“Gate status”) to the COM and 3 I/O terminals of the GATOR; NC – closed state (“NC - status close”)
  • 4 gate control (“Gate control”): the C and NO terminals of the GATOR's 5 OUT relay to terminals 2 and 3 of the gate automation

WP17 GATOR WiFi

The drawing shows the terminal labels of the GV17 GATOR (also called GATOR LTE). On the WP17 GATOR WiFi the corresponding terminals are: +DC, −DC, A RS485 and B RS485 – see the terminal table in the WP17 manual.

3.1 Placement

The compact module can also be fitted inside the gate automation housing, with no separate space or complicated wiring needed. Place it so that the terminal blocks stay accessible and the indicators (POWER, TROUBLE) are visible during servicing.

3.2 Power supply and RS485 bus

  1. Power: the +DC and −DC terminals of the iO4R take 10–26 V DC; in the drawing it is fed from the same 12 V power supply that also powers the GATOR.
  2. RS485 bus: connect the A RS485 terminal of the gate controller to the A (RS485A) terminal of the iO4R, and the B RS485 terminal to the B (RS485B) terminal.

Supply voltage

The iO4R only works on DC voltage (10–26 V DC). The GV17 GATOR can also run on 9–32 V DC or 12–24 V AC: if the gate controller is fed with AC voltage or with a DC voltage outside 10–26 V, the iO4R needs a separate 10–26 V DC power supply.

3.3 Safety sensors and relay outputs

You connect the safety sensors of the gate automation (for example the photocells) to the gate automation through the iO4R:

  1. Connect the output contact of the sensor to one of the iO4R inputs: between the input terminal and the C terminal next to it (in the drawing 1 and C).
  2. Connect the C and NC terminals of the relay with the same number (in the drawing 1C and 1NC) to the safety input of the gate automation, where the sensor output was connected before (in the drawing COM and IN).
  3. The same for more sensors: input 2 goes with output 2 (2NO / 2C / 2NC), input 3 with output 3 (3NO / 3C / 3NC), input 4 with output 4 (4NO / 4C / 4NC).

The inputs also accept EOL wiring (supervised with an end-of-line resistor) with a nominal resistance of 8.2 kΩ; the input voltage can be between 0 V and the supply voltage. Whether the sensor goes to the input with or without an 8.2 kΩ resistor depends on the gate automation. The relays can switch max. 125 V and max. 1 A (at 30 V DC). An 8.2 kΩ resistor can be switched onto the NO terminal of the relay outputs with the “8K2” jumper (1.4) – where the receiving side expects a supervised output.

The iO4R is used to bypass faulty safety sensors. If you bypass a faulty sensor and operate the gate, always make sure that there is no obstacle in the gate's range of movement.

3.4 Gate status sensor and gate control

  • Gate status (3 I/O): connect the contact that signals the gate status (limit switch or the status output of the gate automation) between the COM and 3 I/O terminals of the GATOR. This input provides the gate position and the cycle counting: a cycle only counts if the gate has fully opened and fully closed as well.
  • Gate control (5 OUT): the C and NO terminals of the GATOR's 5 OUT relay go to the control input (open/start) of the gate automation – as described in the gate controller's manual.

Important

In the Protegus 2 monitoring setup, 3 I/O provides the gate position and the cycle counting. If there is a Wiegand reader, the exit button would also go to 3 I/O, but 3 I/O can only do one of the jobs at a time, so you have to choose. If you select 3 I/O as the exit button in the settings, the exit button works, but the gate status is not shown in the app. If you want to see the gate status in the app via 3 I/O, the exit button does not work. If you use the iO4R as a simple expander, you can connect the exit button to 3 I/O. The IN1 and IN2 inputs are reserved for the Wiegand reader.

4. Setup in the Protegus 2 app

You add the gate controller and the iO4R in the Protegus 2 app in one go. Log in with your company or installer account, and keep the gate controller's IMEI number (unique ID) and the iO4R serial number at hand.

4.1 Adding the gate controller

  1. In the list of systems, tap the + button (add a new system).
  2. Enter the gate controller's Unique ID/IMEI, or tap Scan QR Code and scan the QR code on the gate controller's sticker. Tap Next.
Protegus 2 – entering the gate controller's ID
Figure 3. Protegus 2 – entering the ID: the Unique ID/IMEI field with the Scan QR Code button below it; on the sticker drawing, the location of the QR code and the ID.
  1. On the Select the setup mode screen, choose the Advanced Gator Monitoring mode – this is the setup of the iO4R expander with gate monitoring and cycle counting. (Default is the usual system adding, without further settings.)
Protegus 2 – selecting the Advanced Gator Monitoring mode
Figure 4. Protegus 2 – Select the setup mode: the Default (usual adding) and the Advanced Gator Monitoring (setup of the iO4R expander with gate monitoring and cycle counting) mode.

4.2 Gate control and maintenance

On the Gate control and maintenance screen you enter the output that switches the gate, the gate status input and the maintenance cycle count:

  • Output 5 Name – the name of the 5 OUT output that switches the gate (“Gate control” in the example). The users see this name and icon.
  • Gate/Door position input – the gate position is provided by the 3 I/O input, which also counts the cycles. I/O 3 Name: the name of the input (the users see this name and icon); Type: the type of the connected contact (NO in the factory example).
  • Cycles – maintenance is due after this many cycles (3000 in the example). A cycle counts when the gate opens fully and closes fully.

The information box at the bottom (How monitoring works) sums up the same: the 5 OUT output follows the gate status based on the 3 I/O input and counts the full open–close cycles. 3 I/O is for cycle counting and cannot be changed; IN1 and IN2 are reserved for the Wiegand reader. Tap Next.

Protegus 2 – setting up gate control and maintenance cycles
Figure 5. Protegus 2 – Gate control and maintenance: Output 5 Name (the name of the output that switches the gate), the Gate/Door position input group (I/O 3 Name, Type), the Cycles field (maintenance cycle count, 3000 in the example) and the How monitoring works information.

4.3 Setting up the iO4R

  1. On the iO4R Settings screen, tap the Serial number row, enter the iO4R serial number and tap OK.
  2. Switch on the outputs (Output 1 … Output 4) to which you have connected a safety sensor.
Protegus 2 – the iO4R serial number and switching on the outputs
Figure 6. Protegus 2 – iO4R Settings: the Serial number row and the Output 1 … Output 4 switches.
  1. For each output you switched on, enter: - the name of the output (“Output 1 iOx1” in the example) – the users see this name and icon; - the type of the output – Guard in the factory example; - in the Assigned input field, the assigned input (“Input 1 iOx1” in the example) – the input to which the sensor is connected; - in the input's Type field, the contact type (NO in the factory example).
  2. Tap Next.
Protegus 2 – setting up an iO4R output and its assigned input
Figure 7. Protegus 2 – setting up an output: the serial number (000023 in the example), the name (“Output 1 iOx1”) and type (Guard) of Output 1, in the Input group the Assigned input (“Input 1 iOx1”) and the input type (NO); below it the next output (Output 2).

4.4 Finishing the setup

  1. The app writes the settings to the gate controller and restarts it (Restarting device: connecting, preparing, writing successful, restarting). Wait until it finishes.
  2. On the Configuration almost done screen, tap Next. (Further settings are available with the Advanced settings button.)
  3. Enter the name of the system (“Gator” in the example), choose a background and set the time zone, then tap Next (or Skip if you do not want to enter them).
  4. After the System added successfully! message, you can change the default names with the Personalize button, or skip this with the Skip button.
  5. Wait: the system becomes fully operational within 1 minute at most. After that it is shown in Online state, with the gate control button (Gate control in the example).
Protegus 2 – the added GATOR system in Online state
Figure 8. Protegus 2 – the added system: at the top the notice (“It may take up to 1 minute for your system to be fully operational.”), below it the name of the system, its Online state and the Gate control button.

TrikdisConfig

On the Modules page of the GATOR's TrikdisConfig program, the iO4R is also among the selectable modules (as AP-IO4R). You set up the iO4R in Protegus 2, in the Advanced Gator Monitoring mode – and this manual follows that too.

TrikdisConfig – the GATOR Modules page with the AP-IO4R module
Figure 9. TrikdisConfig – the GATOR's Modules page: in the Module drop-down list, AP-IO4R next to the W485, E485, iO-LORA, IO-8 and IO8-Lora modules; beside it the Serial No., Name and Firmware version columns.

5. Handover to the user

At the end of the setup you transfer the system to the user's own Protegus 2 account:

  1. On the system screen, open the menu (☰).
  2. Select Settings.
  3. In the Configure Gator list, tap Transfer system.
Protegus 2 – the Transfer system menu item
Figure 10. Protegus 2 – Configure Gator: the list of system settings (System information, Inputs, Outputs, Users, Cameras, Advanced settings), with Transfer system highlighted.
  1. Enter the user's email address (Email), or select it from the list (Choose from list), then tap Transfer. The address must be registered in Protegus 2.
Protegus 2 – transferring the system by entering an email address
Figure 11. Protegus 2 – Transfer system: transferring the system to the user belonging to the given email address. According to the text, the address must be registered in Protegus 2 (the factory screenshot is from the Protegus2 Beta version); after the transfer you lose control over the system, and all permissions pass to the other user. Below it Choose from list, the Email field and the Transfer button.

After the transfer you lose control over the system, and all permissions pass to the user.

6. Checking gate monitoring and control

After the handover, the user has to log in to Protegus 2 with their own account.

Bypassing a safety sensor can disable the gate's safety protection. Use the bypass only as a temporary, authorized service intervention, and restore the normal operation of the sensors before you hand the system over for regular use.

6.1 Cycles, inputs, control

  1. On the system screen, tap the gate control button (Gate control in the example).
  2. In the Cycles group, Total cycles is the number of cycles counted so far, and Cycles to maintenance is the number of cycles remaining until maintenance (the value entered during setup, 3000 in the example). Below them Input status (state of the inputs), Events and More (further options).
Protegus 2 – gate cycles and the state of the inputs
Figure 12. Protegus 2 – the gate control screen: at the top the gate button, in the Cycles group Total cycles (cycles so far, 0 in the example) and the cycles remaining until maintenance (Cycles to maintenance, 3000 in the example), below them the Input status row.
  1. Tapping the Input status row opens the Input status / bypass screen: at the top the gate status input (I/O 3), below it the four inputs of the iO4R (Input 1 iOx1 … Input 4 iOx4), each with a switch next to it – the bypass of the input is handled from here.
Protegus 2 – the state and bypass of the inputs
Figure 13. Protegus 2 – Input status / bypass: the I/O 3 gate status input and the four inputs of the iO4R (Input 1 iOx1 … Input 4 iOx4), with the switches next to them.
  1. Try the gate control: when you tap the button, the gate operates, and the event log shows who switched it and when (in the example “User Igoris has switched on Gate control” – the user switched on the gate control, with the time).
Protegus 2 – opening the gate and the event line
Figure 14. Protegus 2 – opening the gate: on the system screen the latest event (“User … has switched on Gate control”, with the time) and the Gate control button.

6.2 System check

Before the handover, check the following:

  1. Open and close the gate fully, and see whether the cycle counter changed as expected.
  2. Operate each monitored input of the iO4R one by one (for example obstruct the photocell), and check whether the state of the input changes in Protegus 2.
  3. Try the gate control icon, and check whether the gate automation responds correctly.

7. Troubleshooting and frequently asked questions

The cycle counter does not change
  • A cycle only counts if the gate opens fully and closes fully as well – a movement stopped halfway or reversed is not a cycle.
  • The gate status sensor must be connected to the 3 I/O and COM terminals of the GATOR (section 3.4), and in Protegus 2 the type of I/O 3 (NO or NC) must match the connected contact (section 4.2).
Can the gate status input be moved to another input?

No. In the Protegus 2 monitoring setup, the gate position and the cycle counting can only be provided by 3 I/O; this cannot be moved to another input. IN1 and IN2 belong to the Wiegand reader. 3 I/O can only do one job at a time: if you set it up as the exit button, the gate status is not shown in the app (section 3.4).

The TROUBLE indicator is on

The TROUBLE indicator shows that the RS485 communication with the gate controller has been lost. Check the RS485 wires (the A RS485 terminal of the gate controller to terminal A of the iO4R, B RS485 to terminal B), and whether the iO4R is getting power (POWER).

What should I watch out for when bypassing a sensor?

The bypass can disable the gate's safety protection: use it only as a temporary, authorized service intervention, and before operating the gate make sure there is no obstacle in its range of movement. Restore the normal operation of the sensors before handing the system over for regular use.

Can the iO4R be set up in TrikdisConfig?

The iO4R is also in the Modules list of the GATOR's TrikdisConfig program (as AP-IO4R), but the setup is done in the Advanced Gator Monitoring mode of Protegus 2 (chapter 4).

8. Safety instructions

Attention!

Electricity can be dangerous and may cause personal injury or DEATH, as well as other financial loss or damage if not used or installed properly.

Installation involves working with electrical equipment, and it should be executed in accordance with current regulations!

Warranty validation requires the device to be installed by a qualified person following the installation regulations for electrical equipment and adhering to the current regulations for the safe operation of electrical equipment.

  • The iO4R may only be installed and maintained by qualified persons.
  • Before wiring, disconnect both the mains and the low-voltage power supply.
  • Follow the safety instructions of the gate automation manufacturer and the local electrical regulations.
  • Bypassing a safety sensor can disable the gate's safety protection: use it only as a temporary, authorized service intervention, and restore the normal operation of the sensors before handing the system over for regular use.
  • With a bypassed sensor, always make sure that there is no obstacle in the gate's range of movement before operating the gate.
  • The relay outputs can switch max. 125 V and max. 1 A (at 30 V DC).