FireCom fire communicator – installation and programming manual

Installation and programming manual for the Trikdis FireCom Ethernet and 4G fire communicator (EN 54-21, EN 54-4): power supply and battery, connection to the fire alarm control panel's outputs or RS485 bus (ESPA 4.4.4, NSC Solution, INIM Smartline, C-TEC Cast ZFP, Polon-Alfa 3000), setup in TrikdisConfig, monitoring station, Protegus 2, control by SMS and call.

  • 79 min read
FireCom fire communicator – installation and programming manual

1. Overview

The Trikdis FireCom is an EN 54 certified fire communicator with Ethernet and 4G mobile network (dual SIM) connections.

The FireCom forwards the fire alarm control panel's messages over the local network (LAN) and/or the mobile network to the monitoring station's receiver. How it works: when one of the communicator's inputs (zones) is violated, the FireCom sends an event message over mobile internet and/or the local network to the monitoring station's receiver or to the Protegus 2 app; it can also send SMS messages and make phone calls. The communicator is available with a 4G modem. You make the settings with the TrikdisConfig software, over a USB cable or remotely.

Certification Details
Standard The FireCom meets the requirements of the EN 54-21:2006 and EN 54-4:1997/AC:1999/A1:2002/A2:2006 standards, and fulfils the performance requirements specified for a type 1 transmission system in Annex A of EN 54-21.
Certificate 1922-CPR-2083 – Fire detection and fire alarm systems. Alarm transmission and fault warning routing equipment. Power supply equipment.
Certification body No. 1922 "Dedal" notified product certification body – Nesebar, Mladost str. 50, 8230 Bulgaria
Trikdis technical support support@trikdis.lt, +37067422877

1.1 What it is for and how it works

Connection to the fire alarm control panel

  • Connected to the panel's outputs: the panel's status outputs (alarm, fault, etc.) are connected to the FireCom's inputs (section 3.4).
  • On the RS485 2 bus: to fire alarm control panels using the ESPA 4.4.4 protocol, and to NSC Solution, INIM Smartline, C-TEC Cast ZFP and Polon-Alfa 3000 fire alarm control panels (sections 3.5–3.9); the Polon-Alfa 3000 can also be connected over the local network (LAN).
  • In line with EN 54, two relay outputs signal to the control panel a fault in the connection to the monitoring station and the successful delivery of a message (section 3.12).

Messages to the monitoring station

  • It sends the events through the built-in LAN module or the 4G mobile modem.
  • It sends the events over the available communication channels, in the order you set.
  • Any monitoring station can receive its messages if it has a Trikdis software or IP receiver, or an IP receiver from another manufacturer that supports the SIA DC-09 IP protocol.
  • Reporting to the monitoring station can be given priority: the messages go to the monitoring station first, and only after that to Protegus 2.
  • It can also send events to the receivers of two different monitoring companies.
  • It sends the event messages with Contact ID or SIA codes.

Messages to the users

  • It calls the selected phone numbers (up to 8 users).
  • It sends SMS messages about the events.
  • It sends push notifications and event notifications with special sounds to the Protegus 2 app.
  • Remote temperature monitoring.

Remote control of the outputs

  • from the Protegus 2 app;
  • by calling the device's phone number;
  • by SMS message.

Setup and installation

  • Setup over a USB cable or remotely, with the TrikdisConfig software.
  • Remote firmware update.
  • Two access levels (account types) for the settings: installer and administrator.

Inputs and outputs

  • 3 relay outputs (1 A, 30 V DC).
  • The FLOOP input is for connecting two-wire fire detectors.
  • 10 I/O terminals, each of which can be set as an input (IN) or an output (OUT). Types selectable as an input: NC, NO, EOL, EOL_T, ATZ, ATZ_T. Resistors of different values can be used in the EOL and ATZ circuits.
  • With iO expansion modules the number of inputs (IN) can be extended to 32 and the number of outputs (OUT) to 16.
  • The iO series expansion modules connect to the RS485 bus (A1, B1).
  • The fire alarm control panel connects to the RS485 2 bus (A2, B2).

1.2 Technical specifications

Parameter Value
LTE modem bands EU (Europe): LTE-FDD B1 / B3 / B5 / B7 / B8 / B20 / B28; LA (Latin America): LTE-FDD B2 / B3 / B4 / B5 / B7 / B8 / B28 / B66
Power supply voltage 15–32 V DC, 2.5 A
Current consumption in standby up to 50 mA; while transmitting up to 300 mA; with the maximum load available with external devices up to 2.5 A
Backup power source [BAT] 12 V lead-acid battery, 4 Ah / 7 Ah
Battery charging current up to 500 mA
Voltage and current for external devices [AUX] 12 V DC, up to 1 A
Transmission protocol TRK, SIA DC-09_2007, SIA DC-09_2012, SIA DC-09_IPcom, TL150
Encryption key 6 characters
Connection to the monitoring station TCP/IP or UDP/IP
Event codes Contact ID, SIA
LAN module yes, built-in
LAN network setup DHCP or manual
SIM card 2 pcs, nano size
Reporting destinations the primary and backup receivers of two different monitoring companies; the Protegus 2 cloud, the iOS and Android Protegus 2 app; by SMS to 8 mobile phones; calls 8 mobile phones
Event reporting channels 4G, Ethernet (LAN), SMS, call
Message encryption yes
Internal clock yes
Users 40
Dual-purpose terminals [I/O] 10; the IN or OUT function is selected during programming. For IN the selectable type: NC, NO, EOL, EOL_T, ATZ, ATZ_T. For OUT the terminal is open collector (OC), up to 100 mA
Number of partitions 8
Number of zones 10 (20 with ATZ); can be extended to 32 with expanders
Number of PGM outputs 3 relays (1 A, 30 V DC); 13 if you set the I/O terminals as outputs; can be extended to 16 with expanders
Message buffer 60 events
Event log up to 1000 events; the oldest entries are deleted automatically
Setup remotely with the TrikdisConfig software or locally with a USB Type-C cable
1-Wire data bus length [1 WIRE] up to 30 m
Compatible temperature sensors Maxim® / Dallas® DS18S20, DS18B20; AM2301 series
Number of temperature sensors on the 1-Wire data bus 8 (Dallas), or 1 if you use an AM2301 series sensor
RS485 bus 2
RS485 bus length up to 100 m
Supported modules iO-8 expansion module; iO-MO – iO-WL wireless transceiver; iO-LORA expansion module; iO8-LORA expansion module; PB-LORA panic button; REL-LORA expansion module; fire alarm control panel using the ESPA 4.4.4 protocol; NSC Solution, INIM Smartline, C-TEC Cast ZFP and Polon-Alfa 3000 fire alarm control panels
Operating environment –10 … +50 °C, up to 80 % relative humidity at +20 °C
Dimensions 235 × 205 × 92 mm
Weight 1.35 kg

The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.

Trikdis FireCom Ethernet + 4G fire communicatorTrikdis FireCom Ethernet + 4G fire communicator

1.3 Parts of the communicator

The numbers in the figure mark the parts of the FireCom's printed circuit board. The board is mounted together with the power supply in a metal enclosure (chapter 3).

The FireCom's printed circuit board with the LEDs, the power and battery terminals, the terminal block, the relay outputs, the two SIM holders, the USB and the LAN connector.
Figure 1. The FireCom's printed circuit board.
  • 1 connection and operation LEDs
  • 2 push button – not used
  • 3 backup power supply terminal block
  • 4 main power supply terminal block
  • 5 RESET button
  • 6 external terminal block
  • 7 1-Wire terminal block
  • 8 LAN connector
  • 9 relay output terminal block
  • 10 SIM card holders
  • 11 mobile network (GSM) antenna connector
  • 12 USB Type-C connector

1.4 Terminals

The terminal names are printed on the circuit board, next to the terminal blocks.

Terminal Purpose
+ (power terminal) positive terminal of the power supply (15–32 V DC)
− (power terminal) negative terminal of the power supply (15–32 V DC)
BAT+ positive terminal of the backup power supply (12 V)
BAT− negative terminal of the backup power supply (12 V)
AUX+ 12 V positive power terminal for external devices
AUX− common negative terminal
A1, B1 (RS485) RS485 bus for connecting iO expansion devices
A2, B2 (RS485) RS485 bus for connecting the fire alarm control panel
IO1–IO10 input and output terminals (input by default)
C common negative terminal
AUX+ 12 V positive power terminal for external devices
FLOOP terminal for connecting a two-wire fire detector
+5V 5 V, 0.2 A positive power terminal for 1-Wire devices
1W (1 WIRE) 1-Wire data bus terminal
C common negative terminal
NO1 / C1 / NC1 terminals of PGM relay output 1
NO2 / C2 / NC2 terminals of PGM relay output 2
NO3 / C3 / NC3 terminals of PGM relay output 3

1.5 LEDs

There are five LEDs on the circuit board (SIM, ETH, DAT, STA, FPS) and three on the front of the enclosure (POWER, DATA, TROUBLE). The table describes the DAT / DATA, STA / TROUBLE and FPS / POWER pairs together; where an indication applies to only one of them, its name is given in brackets.

LED Light Meaning
SIM off not connected to the mobile network
green flashing the SIM card is registering on the mobile network
green, steady the SIM card is registered on the mobile network
green steady and yellow flashing connected to the mobile network; on a 4G network, 3 yellow flashes already mean sufficient signal strength
ETH green flashing the LAN cable is not connected, or there is a DHCP error
green, steady connected to the local network (LAN)
DAT / DATA off all event messages have been sent
green, steady a message is being sent
yellow, steady (DAT) there are unsent event messages in the buffer
STA / TROUBLE green, steady (STA) during power-up: the communicator is starting
green flashing (STA) after start-up: no operating fault
off (TROUBLE) no operating fault
1 red flash no SIM card inserted
2 red flashes the SIM card's PIN code is wrong
3 red flashes cannot connect to the mobile network
4 red flashes cannot connect to the IP receiver on the primary channel
5 red flashes cannot connect to the IP receiver on the backup channel
6 red flashes no DC supply voltage
7 red flashes AUX output fault (overcurrent or overvoltage)
8 red flashes battery fault
9 red flashes the LAN cable is not connected
10 red flashes DHCP error on the local network (LAN)
FPS / POWER off the power supply is not connected
green, steady there is no problem with the power supply
1 green flash no mains (AC) supply voltage
2 green flashes the backup power supply voltage is not sufficient

Section 3.14 describes the correct indication after power-up and how to evaluate the signal strength.

1.6 Tools and accessories needed for installation

Before you start the installation, check that you have everything at hand:

  1. a USB Type-C cable for the setup;
  2. a cable with at least 4 cores for connecting the communicator to the fire alarm control panel;
  3. a 2.5 mm flat-blade screwdriver;
  4. an external mobile network antenna if the signal at the site is weak;
  5. an activated nano SIM card (the PIN request can be switched off);
  6. the manual of the fire alarm control panel you are connecting the communicator to.

The listed accessories must be purchased separately – order them from your dealer. If the signal at the site is weak, use an external antenna on a cable that can be placed away from the enclosure:

Trikdis ME301M magnetic antenna with 2,5m wireTrikdis ME301M magnetic antenna with 2,5m wire Trikdis ANT04 GSM stick-on antenna with 2,5m wireTrikdis ANT04 GSM stick-on antenna with 2,5m wire

2. Power supply

2.1 Main power supply

The communicator must be powered from a direct current (DC) power source. For an uninterruptible power supply, a backup power source – a 12 V battery – must be connected to the system. A 12 V, 4 Ah or 7 Ah lead-acid battery is suitable as the backup power source (section 1.2); the note in section 3.1 covers how to choose it.

12 V 7 Ah gel battery for alarm control panel12 V 7 Ah gel battery for alarm control panel

2.2 Backup power supply

If there is a problem with the main power supply, the communicator sends a DC Fault event message and automatically switches over to the 12 V backup battery. If the battery voltage drops to 11.5 V, a Low Battery event message is generated. If the voltage falls below 9.5 V, the battery is disconnected. When the DC supply voltage returns, a DC Restore message is generated and battery charging starts automatically. When the battery voltage reaches 12.6 V, a Battery Restore event message is generated.

2.3 Package contents

Item Quantity
FireCom communicator board with antenna, mounted in a metal enclosure 1 pc
Metal enclosure with a Mean Well switch-mode (pulse) power supply 1 pc
10 kΩ resistor 20 pcs
Wire for connecting the battery 1 pc
Tamper switch 1 pc
Terminal block with a 3.15 A fuse 1 pc
Mounting parts (4 screws, 4 nylon wall plugs) 1 set

The USB cable (Type-C) needed for programming the communicator must be purchased separately.

3. Installation and wiring

Warining!

It is forbidden to perform wiring on a device under voltage. Before starting the work, disconnect power (including backup batteries).

The communicator's printed circuit board is mounted in an enclosure in which the DC power supply with the 3.15 A fuse is already installed, and which also has room for the backup battery. This chapter describes the wiring order; the wiring of detectors, smoke detectors and fire alarm control panels (the panel's outputs, and on the RS485 2 bus the ESPA 4.4.4 protocol, NSC Solution, INIM Smartline, C-TEC Cast ZFP and Polon-Alfa 3000 panels); temperature sensors; the relay and the LED indicator; the panel's inputs; the iO expansion modules; and finally powering up the communicator.

Dimensions of the FireCom board

The figure shows the dimensions of the board and the mounting holes (in millimetres), as well as the position of the holes.

Dimension drawing of the FireCom board with the mounting holes, the SIM holders, the connectors and the terminal blocks.
Figure 2. Dimensions of the FireCom board (mm): the board is 138 × 78.5 mm; the four Ø 4 mm mounting holes are 93 mm apart horizontally and 61 mm apart vertically, the bottom left hole is 5 mm from the left edge and 10 mm from the bottom edge.

3.1 Wiring order

The numbers in the figure are the numbers of the steps below.

FireCom wiring order: SIM card, LAN cable, terminal block, mains power supply and backup battery.
Figure 3. Wiring order: ① the SIM card (nano SIM) into the SIM1 holder; ② LAN cable ("LAN cable"); ③ the terminal block; ④ the ~230 V mains supply through the FU 500 mA 250 V fuse to the DC power supply ("DC power supply", 15–32 V, 1.5 A), whose + and − outputs go to the board's + and − terminals; ⑤ battery ("Battery", 12 V, 7 Ah) to the battery terminals with the polarity shown in the drawing.
  1. If you use a SIM card, insert the activated SIM card into the SIM holder.
  2. If you use a local network (LAN), connect the LAN cable.
  3. Connect the fire detectors, the indicators and the controlled devices according to the wiring diagrams given here and the own wiring diagram of each device to be connected.
  4. Connect the mains (AC) power wires to the terminals.
  5. Place the backup battery in the enclosure. Connect the battery terminals to the communicator's BAT+ / BAT− terminals.

According to the EN 54 standard, the battery must charge to 80 % of its capacity within 24 hours and reach the rest within the following 48 hours – choose a battery that meets this.

What does the network need? The communicator itself initiates the outgoing connection to the monitoring receiver and the Protegus cloud, so no port needs to be opened or forwarded on the router, and neither a public static IP address nor dynamic DNS is needed. What you do need:

  • a free Ethernet port on the router or switch;
  • DHCP (factory setting), or a static IP address, subnet mask, gateway and DNS provided by the network administrator;
  • outgoing traffic allowed to the receiver's address and port (TCP or UDP, depending on the receiver setting), as well as to the Protegus cloud.

On a filtered – corporate or institutional – network, agree on this with the network administrator in advance: home routers allow all outgoing connections by default, but a firewall-protected network may need a separate rule.

3.2 Connecting detectors

On the communicator board, 10 terminals (IO1–IO10, inputs) are used for connecting detector circuits. The number of inputs can be increased to 32 with input expanders (iO-8, iO-MO, iO-LORA, iO8-LORA). Any terminal can be set as an input and given zone properties: the circuit type (NO, NC, EOL, EOL_T, ATZ, ATZ_T) and the sensitivity to transient circuit events (section 6.6, Zones page).

The wiring diagrams of the detectors follow. The selectable values of the resistors (RT – tamper, R1 – detector 1, R2 – detector 2):

RT R1 R2
2.2 kΩ 2.2 kΩ 4.7 kΩ
1 kΩ 1 kΩ 2.2 kΩ
5.6 kΩ 5.6 kΩ 3.3 kΩ
5.6 kΩ 3.3 kΩ 5.6 kΩ
3.3 kΩ 6.8 kΩ 3.3 kΩ
2.2 kΩ 4.7 kΩ 8.2 kΩ
10 kΩ 10 kΩ 5.6 kΩ

You enter the values used in the EOL Type field of the System Options page (section 6.2).

**NO** – normally open contact between the **IOx** input and the **C** common terminal, without a resistor.
Figure 4. NO – normally open contact between the IOx input and the C common terminal, without a resistor.
**NC** – normally closed contact between **IOx** and **C**, without a resistor.
Figure 5. NC – normally closed contact between IOx and C, without a resistor.
**EOL** – NO contact with an end-of-line resistor: the contact and the **R1** resistor in parallel between **IOx** and **C**.
Figure 6. EOL – NO contact with an end-of-line resistor: the contact and the R1 resistor in parallel between IOx and C.
**EOL** – NC contact with an end-of-line resistor: the contact and the **R1** resistor in series.
Figure 7. EOL – NC contact with an end-of-line resistor: the contact and the R1 resistor in series.
**EOL_T** – NC contact with an end-of-line resistor, with tamper and wiring fault detection: from **IOx** the NC tamper contact and **RT** in series, then **R1** in parallel with the second NC contact, towards **C**.
Figure 8. EOL_T – NC contact with an end-of-line resistor, with tamper and wiring fault detection: from IOx the NC tamper contact and RT in series, then R1 in parallel with the second NC contact, towards C.
  • T tamper contact ("Tamper"), signals that the detector cover has been opened
**ATZ** – two detectors on one input, with NC contacts, without tamper monitoring: the NC contact of detector 1 in parallel with **R1**, that of detector 2 with **R2**; the two circuits in series between **IOx** and **C**.
Figure 9. ATZ – two detectors on one input, with NC contacts, without tamper monitoring: the NC contact of detector 1 in parallel with R1, that of detector 2 with R2; the two circuits in series between IOx and C.
  • 1 circuit of detector 1 ("Detector terminal 1")
  • 2 circuit of detector 2 ("Detector terminal 2")
**ATZ_T** – two detectors on one input, with NC contacts, end-of-line termination, tamper and wiring fault detection: at detector 1 the NC tamper contact and **RT** in series, then the NC contact in parallel with **R1**; at detector 2 the NC tamper contact in series, then the NC contact in parallel with **R2**.
Figure 10. ATZ_T – two detectors on one input, with NC contacts, end-of-line termination, tamper and wiring fault detection: at detector 1 the NC tamper contact and RT in series, then the NC contact in parallel with R1; at detector 2 the NC tamper contact in series, then the NC contact in parallel with R2.
  • T tamper contact ("Tamper"), signals that the detector cover has been opened
  • 1 circuit of detector 1 ("Detector terminal 1")
  • 2 circuit of detector 2 ("Detector terminal 2")

3.3 Connecting smoke detectors

Two-wire smoke detectors on the FLOOP terminal

If you use this wiring, on the Zones page you must select the FC Fire sensor (FLOOP input) input as the zone's input (Input) (section 6.6). The alarm current of the fire detector must be greater than 10 mA. Up to 8 fire detectors can be connected to the FLOOP terminal.

Two-wire smoke detectors on the **FLOOP** terminal: **AUX+** goes to the **+ IN** terminal of the first detector, **FLOOP** to its **− IN** terminal; the **+ OUT** and **− OUT** terminals of each detector go to the input of the next detector; a 2.2 kΩ end-of-line resistor is placed between the **+ OUT** and **− OUT** terminals of the last detector.
Figure 11. Two-wire smoke detectors on the FLOOP terminal: AUX+ goes to the + IN terminal of the first detector, FLOOP to its − IN terminal; the + OUT and − OUT terminals of each detector go to the input of the next detector; a 2.2 kΩ end-of-line resistor is placed between the + OUT and − OUT terminals of the last detector.
  • EOL 2.2 kΩ end-of-line resistor ("End of line resistor")

Two-wire smoke detectors with an SM1 relay module

If you connect the smoke detector circuit to a selected input, the input (IOx) must be enabled and the circuit type must be set (NO, NC, EOL, EOL_T, ATZ, ATZ_T; section 6.6, Zones page). If you connect the power circuit of the smoke detectors to the PGM output (IO10), the Fire Sensor Reset function must be assigned to the output (section 6.7, PGM page).

The K1 relay is used to detect a cable break and the removal of a fire detector. If you do not use a relay (K1), the K1 contact must be short-circuited.

Two-wire smoke detectors with an **SM1** relay module and a **K1** relay, using the **NC** contact of the SM1. Power: **AUX+** goes to the **+12V** terminal of the SM1 and the **+ IN** terminal of the first detector, **IO10** to the **−12V** terminal of the SM1 and to one end of the K1 coil; the **R** terminal of the SM1 goes to the **− IN** terminal of the first detector; both **OUT** wires continue to the second detector, whose **+ OUT** terminal goes to the other end of the K1 coil, and no wire continues from its **− OUT** terminal. Monitored input: **IOx** goes to the **C** terminal of the SM1, and the **NC** terminal of the SM1 goes through the K1 contact and the **R1** end-of-line resistor (in series) to the FireCom's **C** terminal.
Figure 12. Two-wire smoke detectors with an SM1 relay module and a K1 relay, using the NC contact of the SM1. Power: AUX+ goes to the +12V terminal of the SM1 and the + IN terminal of the first detector, IO10 to the −12V terminal of the SM1 and to one end of the K1 coil; the R terminal of the SM1 goes to the − IN terminal of the first detector; both OUT wires continue to the second detector, whose + OUT terminal goes to the other end of the K1 coil, and no wire continues from its − OUT terminal. Monitored input: IOx goes to the C terminal of the SM1, and the NC terminal of the SM1 goes through the K1 contact and the R1 end-of-line resistor (in series) to the FireCom's C terminal.
  • R K1 relay ("Relay") – its role is in the note above
  • EOL the R1 end-of-line resistor ("End of line resistor")

Or:

The same with the **NO** contact of the SM1: **IOx** goes to the **C** terminal of the SM1, the **NO** terminal of the SM1 to the FireCom's **C** terminal; the series branch of the K1 contact and the **R1** end-of-line resistor is between **IOx** and **C**.
Figure 13. The same with the NO contact of the SM1: IOx goes to the C terminal of the SM1, the NO terminal of the SM1 to the FireCom's C terminal; the series branch of the K1 contact and the R1 end-of-line resistor is between IOx and C.
  • R K1 relay ("Relay") – its role is in the note above
  • EOL the R1 end-of-line resistor ("End of line resistor")

Four-wire smoke detectors

If you connect the smoke detector circuit to a selected input, the input (IOx) must be enabled and the circuit type must be set (NO, NC, EOL, EOL_T, ATZ, ATZ_T; section 6.6, Zones page). If you connect the power circuit of the four-wire smoke detectors to the PGM output (IO10), the Fire Sensor Reset function must be assigned to the output (section 6.7, PGM page).

Here too, the K1 relay is used to detect a cable break and the removal of a fire detector. If you do not use a relay (K1), the K1 contact must be short-circuited.

Four-wire smoke detectors and a **K1** relay. Power: **AUX+** goes to the **+ IN** terminal of the first detector, **IO10** to its **− IN** terminal; the **OUT** terminals go to the second detector, and the K1 coil is placed between its **+ OUT** and **− OUT** terminals. Alarm loop: **IOx** and **C** go to the contact input of the first detector and continue to the second detector; the contact of each detector bridges the alarm pair; the series branch of the **R1** end-of-line resistor and the K1 contact is placed across the last **OUT** pair.
Figure 14. Four-wire smoke detectors and a K1 relay. Power: AUX+ goes to the + IN terminal of the first detector, IO10 to its − IN terminal; the OUT terminals go to the second detector, and the K1 coil is placed between its + OUT and − OUT terminals. Alarm loop: IOx and C go to the contact input of the first detector and continue to the second detector; the contact of each detector bridges the alarm pair; the series branch of the R1 end-of-line resistor and the K1 contact is placed across the last OUT pair.
  • R K1 relay ("Relay") – its role is in the note above
  • EOL the R1 end-of-line resistor ("End of line resistor")

3.4 Connecting to the outputs of the fire alarm control panel

If you want to monitor the state of the fire alarm control panel, connect the appropriate outputs of the panel to the FireCom's inputs. The panel's outputs (PGM1, PGM2, PGM3) must be set as status outputs (alarm, fault, etc.) in the panel. The drawing comes in two versions: when the FireCom is powered from the panel's 24 V (without the built-in power supply), and when it runs from its own built-in power supply.

Connection to the outputs of the fire alarm control panel (**Fire control panel**), without the built-in power supply: the panel's **+24 V** terminal goes to the FireCom's **+DC** terminal, **GND** to the **−DC** terminal; one terminal of the **PGM1**, **PGM2** and **PGM3** outputs goes to the **IO1**, **IO2** and **IO3** input respectively, the other to the **C** common terminal; an **R1** resistor is placed in parallel across the two terminals of each output (values: section 3.2); the middle terminal of the PGM outputs is not connected.
Figure 15. Connection to the outputs of the fire alarm control panel (Fire control panel), without the built-in power supply: the panel's +24 V terminal goes to the FireCom's +DC terminal, GND to the −DC terminal; one terminal of the PGM1, PGM2 and PGM3 outputs goes to the IO1, IO2 and IO3 input respectively, the other to the C common terminal; an R1 resistor is placed in parallel across the two terminals of each output (values: section 3.2); the middle terminal of the PGM outputs is not connected.
The same with the built-in power supply: power is not wired from the panel; the **PGM1–PGM3** outputs go to the **IO1–IO3** inputs and the **C** terminal in the same way, with a parallel **R1** resistor; the middle terminals are not connected here either.
Figure 16. The same with the built-in power supply: power is not wired from the panel; the PGM1–PGM3 outputs go to the IO1–IO3 inputs and the C terminal in the same way, with a parallel R1 resistor; the middle terminals are not connected here either.

3.5 Fire alarm control panel with the ESPA 4.4.4 protocol

Connect the fire alarm control panel using the ESPA 4.4.4 protocol to the FireCom on the RS485 2 bus (A2, B2), according to the drawings below.

Connecting the panel with the ESPA 4.4.4 protocol (**ESPA4.4.4**) without the built-in power supply: the panel's **+24V** terminal to the FireCom's **+DC** terminal, **0V** to the **−DC** terminal; RS485 – the panel's **A** terminal to **A2**, **B** to **B2**.
Figure 17. Connecting the panel with the ESPA 4.4.4 protocol (ESPA4.4.4) without the built-in power supply: the panel's +24V terminal to the FireCom's +DC terminal, 0V to the −DC terminal; RS485 – the panel's A terminal to A2, B to B2.
The same with the built-in power supply: the panel's **0V** terminal to the FireCom's **C** terminal; RS485 – **A** to **A2**, **B** to **B2**.
Figure 18. The same with the built-in power supply: the panel's 0V terminal to the FireCom's C terminal; RS485 – A to A2, B to B2.

Setting up the FireCom in TrikdisConfig when it is connected to a fire alarm control panel with the ESPA 4.4.4 protocol:

  1. In the RS485 2 interface group of the Modules page, select the ESPA 4.4.4 protocol.
  2. Select the connection type (Connection).
  3. The data transmission settings of the FireCom and the fire alarm control panel must be identical.
TrikdisConfig – **Modules**, **RS485 2 interface** group.
Figure 19. TrikdisConfig – Modules, RS485 2 interface group.
  • 1 Interface type – selecting ESPA 4.4.4
  • 2 Connection – the connection type (RS485 in the picture)
  • 3 data transmission settings (in the picture Baudrate 9600, 8 data bits, None parity, 1 stop bit, Delay 0 ms)
  1. On the Users & Reporting page, enter the phone numbers and e-mail addresses of the users who receive messages from the FireCom (section 6.4).
  2. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox on the SMS & Call reporting tab of the System events page.
TrikdisConfig – **System events**, **SMS & Call reporting** tab: for user 1, at event 19 (**ESPA 4.4.4 text**) **SMS** is ticked and **Call** is empty.
Figure 20. TrikdisConfig – System events, SMS & Call reporting tab: for user 1, at event 19 (ESPA 4.4.4 text) SMS is ticked and Call is empty.
  • 5 the SMS and Call checkboxes
  1. If the messages must also reach the monitoring station's receiver, set up the communication channel on the Reporting to CMS page (sections 4.2 and 6.3). The event messages are sent with the SIA DC-09 protocol.

Test the system: trigger a fire alarm and check that the FireCom's messages arrive at the monitoring station and in Protegus 2.

3.6 NSC Solution fire alarm control panel

Connect the NSC Solution fire alarm control panel to the FireCom on the RS485 2 bus, according to the drawings below.

Connecting the NSC Solution panel without the built-in power supply: the panel's **+24V** terminal to the FireCom's **+DC** terminal, **0V** to the **−DC** terminal; RS485 – **A** to **A2**, **B** to **B2**.
Figure 21. Connecting the NSC Solution panel without the built-in power supply: the panel's +24V terminal to the FireCom's +DC terminal, 0V to the −DC terminal; RS485 – A to A2, B to B2.
The same with the built-in power supply: the panel's **0V** terminal to the FireCom's **C** terminal; RS485 – **A** to **A2**, **B** to **B2**.
Figure 22. The same with the built-in power supply: the panel's 0V terminal to the FireCom's C terminal; RS485 – A to A2, B to B2.

Setting up the FireCom in TrikdisConfig when it is connected to an NSC Solution fire alarm control panel:

  1. In the RS485 2 interface group of the Modules page, select the NSC solution panel.
  2. The NSC slave address (the communicator's slave address) must not be the same as the address of the modules connected to the fire alarm control panel.
TrikdisConfig – **Modules**, **RS485 2 interface** group.
Figure 23. TrikdisConfig – Modules, RS485 2 interface group.
  • 1 Interface type – selecting NSC solution
  • 2 NSC slave address – 10 in the picture
  1. On the Users & Reporting page, enter the phone numbers and e-mail addresses of the users who receive messages from the FireCom (section 6.4).
  2. The users receive SMS messages and calls about the ticked events (Users & Reporting page, SMS for Panel events tab). In the CID column you can add further Contact ID event codes; next to the new codes you must also enter the SMS text. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox.
TrikdisConfig – **Users & Reporting**, **SMS for Panel events** tab: for user 1, at the visible events (**E110** fire alarm, **E118** fire pre-alarm, **E380** detector fault, **E323** line fault, **E301** mains power loss, **E302** low battery voltage, **E311** missing battery) **SMS** is ticked and **Call** is empty.
Figure 24. TrikdisConfig – Users & Reporting, SMS for Panel events tab: for user 1, at the visible events (E110 fire alarm, E118 fire pre-alarm, E380 detector fault, E323 line fault, E301 mains power loss, E302 low battery voltage, E311 missing battery) SMS is ticked and Call is empty.
  • 4 the SMS and Call columns of user 1
  1. If the messages must also reach the monitoring station's receiver, set up the communication channel on the Reporting to CMS page (sections 4.2 and 6.3).

After setting up the FireCom, switch on the power of the fire alarm control panel and wait until the panel's software has loaded. Then the modules connected to the RS485 bus must be searched for (scanned) on the panel. On the panel press: PROG. > INSTALLER > (enter the installer code) 00000 OK > (select) SETTINGS > ENTER > (select) SCAN RS485 > ENTER. Wait until the search has finished, then press the CANCEL button twice to return to the main screen.

Test the system: trigger a fire alarm and check that the FireCom's messages arrive at the monitoring station and in Protegus 2.

3.7 INIM Smartline fire alarm control panel

Connect the INIM Smartline fire alarm control panel to the FireCom on the RS485 2 bus, according to the drawings below.

Connecting the INIM Smartline panel without the built-in power supply: the panel's **13 +24** terminal to the FireCom's **+DC** terminal, **16 GND** to the **−DC** terminal; RS485 – **15 +RS485** to **A2**, **14 −RS485** to **B2**. The crossing wires do not touch.
Figure 25. Connecting the INIM Smartline panel without the built-in power supply: the panel's 13 +24 terminal to the FireCom's +DC terminal, 16 GND to the −DC terminal; RS485 – 15 +RS485 to A2, 14 −RS485 to B2. The crossing wires do not touch.
The same with the built-in power supply: the panel's **16 GND** terminal to the FireCom's **C** terminal; RS485 – **15 +RS485** to **A2**, **14 −RS485** to **B2**.
Figure 26. The same with the built-in power supply: the panel's 16 GND terminal to the FireCom's C terminal; RS485 – 15 +RS485 to A2, 14 −RS485 to B2.

If you connect the INIM Smartline panel to the FireCom on the RS485 bus, the panel must be set to slave mode – you can do this in the panel's SmartLeague software.

SmartLeague – **RS485 Bus Programming** window: in the **Master/Slave Settings** group **Configure as Slave** is selected, **Assign address**: 1.
Figure 27. SmartLeague – RS485 Bus Programming window: in the Master/Slave Settings group Configure as Slave is selected, Assign address: 1.
  • If repeaters are connected to the INIM Smartline panel, the FireCom cannot be connected on the RS485 bus.
  • If the FireCom is connected to the INIM Smartline panel on the RS485 bus, the iO expansion modules are not supported.

Setting up the FireCom in TrikdisConfig when it is connected to an INIM Smartline fire alarm control panel:

  1. In the RS485 2 interface group of the Modules page, select the INIM smartline panel.
TrikdisConfig – **Modules**, **RS485 2 interface** group.
Figure 28. TrikdisConfig – Modules, RS485 2 interface group.
  • 1 Interface type – selecting INIM smartline
  1. On the Users & Reporting page, enter the phone numbers and e-mail addresses of the users who receive messages from the FireCom (section 6.4).
  2. The users receive SMS messages and calls about the ticked events (Users & Reporting page, SMS for Panel events tab; the picture of the tab is in section 3.6). In the CID column you can add further Contact ID event codes; next to the new codes you must also enter the SMS text. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox.
  3. If the messages must also reach the monitoring station's receiver, set up the communication channel on the Reporting to CMS page (sections 4.2 and 6.3).

Test the system: trigger a fire alarm and check that the FireCom's messages arrive at the monitoring station and in Protegus 2.

3.8 C-TEC Cast ZFP fire alarm control panel

Connect the C-TEC Cast ZFP fire alarm control panel to the FireCom on the RS485 2 bus, according to the drawings below.

Connecting the C-TEC Cast ZFP panel without the built-in power supply: the panel's **+24V** terminal to the FireCom's **+DC** terminal, **0V** to the **−DC** terminal (the positive wire is marked +24 V); **ABUS RS485** – the panel's **A** terminal to **A2**, **B** to **B2**.
Figure 29. Connecting the C-TEC Cast ZFP panel without the built-in power supply: the panel's +24V terminal to the FireCom's +DC terminal, 0V to the −DC terminal (the positive wire is marked +24 V); ABUS RS485 – the panel's A terminal to A2, B to B2.
The same with the built-in power supply: the panel's **0V** terminal to the FireCom's **C** terminal; **ABUS RS485** – **A** to **A2**, **B** to **B2**.
Figure 30. The same with the built-in power supply: the panel's 0V terminal to the FireCom's C terminal; ABUS RS485 – A to A2, B to B2.

Setting up the FireCom in TrikdisConfig when it is connected to a C-TEC Cast ZFP fire alarm control panel:

  1. In the RS485 2 interface group of the Modules page, select the C-TEC Cast ZFP panel.
TrikdisConfig – **Modules**, **RS485 2 interface** group.
Figure 31. TrikdisConfig – Modules, RS485 2 interface group.
  • 1 Interface type – selecting C-TEC Cast ZFP
  1. On the Users & Reporting page, enter the phone numbers and e-mail addresses of the users who receive messages from the FireCom (section 6.4).
  2. The users receive SMS messages and calls about the ticked events (Users & Reporting page, SMS for Panel events tab; the picture of the tab is in section 3.6). In the CID column you can add further Contact ID event codes; next to the new codes you must also enter the SMS text. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox.
  3. If the messages must also reach the monitoring station's receiver, set up the communication channel on the Reporting to CMS page (sections 4.2 and 6.3).

Setting up the panel with the ZFPtools software

Install the ZFPtools software on the computer and start it. Switch on the power of the fire alarm control panel and wait until the panel's software has loaded. Connect the panel to the computer with a USB 2.0 A-B cable. The marker numbers in the pictures are the numbers of the steps.

  1. Open the Node View tab.
ZFP Programming Tools, **Site Details** window – the **Node View** tab.
Figure 32. ZFP Programming Tools, Site Details window – the Node View tab.
  • 1 Node View
  1. Download the panel's settings to the computer.
ZFP Programming Tools – **Node View**, **Panel 1**.
Figure 33. ZFP Programming Tools – Node View, Panel 1.
  • 2 Retrieve All Data – downloading the panel's settings
  1. Enter the code (4444 by default).
  2. Click the OK button.
**Panel Log In** window: **Enter Access Level 3 Code** – the access level 3 code.
Figure 34. Panel Log In window: Enter Access Level 3 Code – the access level 3 code.
  • 3 the code fields
  • 4 OK (green tick)
  1. Select the BMS Interface item.
  2. Click a free icon.
ZFP Programming Tools – **Node View**, **Devices**.
Figure 35. ZFP Programming Tools – Node View, Devices.
  • 5 BMS Interface in the Device Palette list
  • 6 a free slot in the Devices area (number 16 in the picture)
  1. Click the Edit Devices button.
ZFP Programming Tools – slot 16 already shows the **BMS Interface** icon.
Figure 36. ZFP Programming Tools – slot 16 already shows the BMS Interface icon.
  • 7 Edit Devices
  1. On the Device tab, enter the name of the system.
**Device Properties**, **Device** tab: **Device Type**: BMS Interface.
Figure 37. Device Properties, Device tab: Device Type: BMS Interface.
  • 8 Name – the name of the system (FIRECOM in the picture)
  1. On the Properties tab, enter the name of the system.
  2. Specify the ABUS RS485 bus to which the FireCom is connected.
  3. Set up the messages.
  4. Write the settings to the panel.
**Device Properties**, **Properties** tab; in the picture **BAUD Rate** 57600, **Response Timeout** 250, **Max Retries** 5.
Figure 38. Device Properties, Properties tab; in the picture BAUD Rate 57600, Response Timeout 250, Max Retries 5.
  • 9 Name – the name of the system (FIRECOM)
  • 10 Connection – ABUS RS485
  • 11 the messages: Zone Disablements – Reports Zone; Input Group Disablements, Output Group Disablements, Group Actions – Reports Group
  • 12 Send All Data – writing the settings to the panel
  1. Enter the code (4444 by default).
  2. Click the OK button (the Panel Log In window is the same as in steps 3–4).

The panel is programmed. Unplug the USB 2.0 A-B cable from the panel.

Test the system: trigger a fire alarm and check that the FireCom's messages arrive at the monitoring station and in Protegus 2.

3.9 Polon-Alfa 3000 fire alarm control panel

Connection on the RS485 bus

The FireCom connects to the Polon-Alfa 3000 panel on the RS485 bus.

Connecting the Polon-Alfa 3000 (**MSO-30** and **MK-30** modules) on the RS485 bus. Power: the **Z1 24V ZEW +** terminal of the MSO-30 to the FireCom's **+** terminal (15–32 V DC, 2.5 A), **Z1 −** to the **−** terminal; RS485 – the **Z1 RS485 A** terminal of the MK-30 to **A2**, **B** to **B2**. The **GND** terminal of the MK-30 is not connected.
Figure 39. Connecting the Polon-Alfa 3000 (MSO-30 and MK-30 modules) on the RS485 bus. Power: the Z1 24V ZEW + terminal of the MSO-30 to the FireCom's + terminal (15–32 V DC, 2.5 A), Z1 − to the − terminal; RS485 – the Z1 RS485 A terminal of the MK-30 to A2, B to B2. The GND terminal of the MK-30 is not connected.

Setting up the FireCom in TrikdisConfig:

  1. In the RS485 2 interface group of the Modules page, select the Polon-Alfa 3000 panel.
  2. As the connection type (Connection), select RS485.
TrikdisConfig – **Modules**, **RS485 2 interface** group.
Figure 40. TrikdisConfig – Modules, RS485 2 interface group.
  • 1 Interface type – selecting Polon-Alfa 3000
  • 2 Connection – RS485
  1. On the Users & Reporting page, enter the phone numbers and e-mail addresses of the users who receive messages from the FireCom (section 6.4).
  2. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox (System events page, SMS & Call reporting tab, section 6.9).
  3. If the messages must also reach the monitoring station's receiver, set up the communication channel on the Reporting to CMS page (sections 4.2 and 6.3).

The Polon-Alfa 3000 panel with the MK-30 module must be set up in the POLON Studio software to work with the Modbus RTU (RS485) protocol.

POLON Studio – the window of the **MK-30 (1)** module: **Modbus Interface**: RS-485; **Modbus RTU Bitrate** 115200, **Parity** None, **Stop Bits** 1, **Address** 1.
Figure 41. POLON Studio – the window of the MK-30 (1) module: Modbus Interface: RS-485; Modbus RTU Bitrate 115200, Parity None, Stop Bits 1, Address 1.

Test the system: trigger a fire alarm and check that the FireCom's messages arrive at the monitoring station and in Protegus 2.

Connection over the local network (LAN)

The FireCom and the Polon-Alfa 3000 panel connect to the same local network (LAN).

The Polon-Alfa 3000 (**MSO-30** / **MK-30**) and the FireCom on the same local network: the **LAN** connector of the MK-30 and the **LAN** connector of the FireCom are connected with LAN cables to the same router (**ROUTER**).
Figure 42. The Polon-Alfa 3000 (MSO-30 / MK-30) and the FireCom on the same local network: the LAN connector of the MK-30 and the LAN connector of the FireCom are connected with LAN cables to the same router (ROUTER).
  • 1 LAN cable ("LAN cable")

Setting up the FireCom in TrikdisConfig:

  1. In the RS485 2 interface group of the Modules page, select the Polon-Alfa 3000 panel.
  2. As the connection type (Connection), select TCP.
  3. Enter the IP address of the Polon-Alfa 3000 panel (IP address).
TrikdisConfig – **Modules**, **RS485 2 interface** group.
Figure 43. TrikdisConfig – Modules, RS485 2 interface group.
  • 1 Interface type – selecting Polon-Alfa 3000
  • 2 Connection – TCP
  • 3 IP address – the IP address of the panel (192.168.1.2 in the picture)
  1. On the Settings tab of the Reporting to CMS page, in the LAN network parameters group, tick the DHCP checkbox (automatic registration mode): this way the FireCom reads the network settings (subnet mask, gateway) automatically and gets an IP address (section 6.3).
  2. On the Users & Reporting page, enter the phone numbers and e-mail addresses of the users who receive messages from the FireCom (section 6.4).
  3. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox (System events page, SMS & Call reporting tab, section 6.9).
  4. If the messages must also reach the monitoring station's receiver, set up the communication channel on the Reporting to CMS page (sections 4.2 and 6.3).

The Polon-Alfa 3000 panel with the MK-30 module must be set up in the POLON Studio software to work on the local network (LAN). Enter the LAN IP addresses according to the settings of your own network.

POLON Studio – the window of the **MK-30 (1)** module: **Modbus TCP IP** 192.168.1.2, **Modbus TCP Mask** 255.255.255.0, **Modbus TCP Gate** 192.168.1.1, **Modbus TCP Port** 502.
Figure 44. POLON Studio – the window of the MK-30 (1) module: Modbus TCP IP 192.168.1.2, Modbus TCP Mask 255.255.255.0, Modbus TCP Gate 192.168.1.1, Modbus TCP Port 502.

Test the system: trigger a fire alarm and check that the FireCom's messages arrive at the monitoring station and in Protegus 2.

3.10 Connecting a temperature sensor

Connect the temperature sensors according to the drawings.

Connecting the **DS18B20** temperature sensor: red wire – **+5V** to the **+Vdd** terminal; yellow – **1W** to the **DQ** terminal; black – **C** to the **GND** terminal.
Figure 45. Connecting the DS18B20 temperature sensor: red wire – +5V to the +Vdd terminal; yellow – 1W to the DQ terminal; black – C to the GND terminal.
  • red wire ("Red wire")
  • yellow wire ("Yellow wire")
  • black wire ("Black wire")
Connecting the **AM2301** temperature and humidity sensor in the same way: red – **+5V** to **+Vdd**; yellow – **1W** to **DQ**; black – **C** to the **GND** terminal.
Figure 46. Connecting the AM2301 temperature and humidity sensor in the same way: red – +5V to +Vdd; yellow – 1W to DQ; black – C to the GND terminal.
  • red wire ("Red wire")
  • yellow wire ("Yellow wire")
  • black wire ("Black wire")

Up to 8 Maxim® / Dallas® DS18S20 or DS18B20 temperature sensors, or up to 1 AM2301 humidity and temperature sensor, can be connected to the FireCom. If you connect the sensor with a wire longer than 0.5 m, we recommend a twisted-pair cable (UTP 4×2×0.5 or STP 4×2×0.5). The board's +5V terminal supplies 5 V DC to the devices connected to the 1-Wire data bus; the maximum output current is 0.2 A. The output is protected against overload: if the current exceeds the maximum permitted value, the power is switched off automatically. The communicator detects and assigns the connected devices automatically (the AM2301 must be assigned manually on the Sensors page, section 6.8).

DS18B20 temperature sensor with 1m wireDS18B20 temperature sensor with 1m wire

3.11 Connecting a relay and an LED indicator

With the relay contacts you can switch various electrical devices remotely (on/off). The communicator's universal I/O terminal must be set as an output (OUT), and the Remote control definition must be assigned to it (PGM page, Output definition, section 6.7).

Connecting an external relay: one end of the coil goes to **AUX+**, the other to the **IOx** terminal; the relay contacts: **NC**, **C**, **NO**.
Figure 47. Connecting an external relay: one end of the coil goes to AUX+, the other to the IOx terminal; the relay contacts: NC, C, NO.
  • R relay ("Relay")
Connecting an LED indicator: from the **AUX+** terminal through a **2k2** (2.2 kΩ) resistor and the LED, in series, to the **IOx** terminal.
Figure 48. Connecting an LED indicator: from the AUX+ terminal through a 2k2 (2.2 kΩ) resistor and the LED, in series, to the IOx terminal.

3.12 Connecting the inputs of the fire alarm control panel

According to the EN 54 standard, the fire alarm control panel must be informed by the communicator about a fault in the connection to the monitoring station, and about the monitoring station having successfully received the messages. For this, the communicator's PGM outputs (for example the Relay1 and Relay2 outputs) must be connected to the dedicated inputs of the fire alarm control panel. The Relay1 PGM output must be set to CMS fail (fault in the connection to the monitoring station), and Relay2 to ACK received (acknowledgement received) (PGM page, section 6.7). The Relay1 output switches on when the communication channel to the monitoring station is interrupted; the Relay2 output switches on for 5 seconds when the message has successfully reached the monitoring station.

Connecting the communicator's relay outputs to the inputs of the fire alarm control panel (**Fire control panel**). **Relay1**: the panel's **C** terminal to **C1**, **IN1** to **NO1**, with an **R1** resistor in parallel between **C1** and **NO1**; **Relay2**: **C** to **C2**, **IN2** to **NO2**, also with an **R1** between **C2** and **NO2**. **IN3**, **NC1** and **NC2** are not connected.
Figure 49. Connecting the communicator's relay outputs to the inputs of the fire alarm control panel (Fire control panel). Relay1: the panel's C terminal to C1, IN1 to NO1, with an R1 resistor in parallel between C1 and NO1; Relay2: C to C2, IN2 to NO2, also with an R1 between C2 and NO2. IN3, NC1 and NC2 are not connected.
  • R the communicator's relay output ("Relay"): Relay1 at the top, Relay2 at the bottom

3.13 Connecting iO series expansion modules

If the FireCom needs more inputs (IN) or outputs (OUT), connect a wired or wireless Trikdis iO series input and output expander to it. Section 6.5 (Modules page) describes how to set up the expansion modules in the FireCom.

Connecting the **iO-8**: power – **AUX+** (+12 V) to the **+DC** terminal of the iO-8, **AUX−** to the **−DC** terminal; RS485 – **A1** to **A**, **B1** to the **B** terminal.
Figure 50. Connecting the iO-8: power – AUX+ (+12 V) to the +DC terminal of the iO-8, AUX− to the −DC terminal; RS485 – A1 to A, B1 to the B terminal.
Connecting the **iO-MO**: power – **AUX+** (+12 V) to **+DC**, **AUX−** to the **−DC** terminal; RS485 – **A1** to **A RS485**, **B1** to the **B RS485** terminal.
Figure 51. Connecting the iO-MO: power – AUX+ (+12 V) to +DC, AUX− to the −DC terminal; RS485 – A1 to A RS485, B1 to the B RS485 terminal.
Trikdis iO8 wired expander moduleTrikdis iO8 wired expander module

Connecting the LORA modules: the RF-LORA transceiver is placed on the RS485 bus and keeps a radio connection, up to 5000 m, with the iO-LORA, iO8-LORA and REL-LORA expanders and the PB-LORA panic button.

Connecting the LORA modules: power – **AUX+** (+12 V) to the **+DC** terminal of the RF-LORA, **AUX−** to the **−DC** terminal; RS485 – **A1** to **A RS485**, **B1** to the **B RS485** terminal. Radio connection up to 5000 m with the **iO-LORA**, **iO8-LORA**, **PB-LORA** and **REL-LORA** modules (in the drawing the module names are preceded by the marks 1*, 2*, 3*, 8*); the iO-LORA and the iO8-LORA get their own 12–26 V power (**+DC**, **−DC**), the REL-LORA 100–230 V AC mains power (**L**, **N**).
Figure 52. Connecting the LORA modules: power – AUX+ (+12 V) to the +DC terminal of the RF-LORA, AUX− to the −DC terminal; RS485 – A1 to A RS485, B1 to the B RS485 terminal. Radio connection up to 5000 m with the iO-LORA, iO8-LORA, PB-LORA and REL-LORA modules (in the drawing the module names are preceded by the marks 1, 2, 3, 8); the iO-LORA and the iO8-LORA get their own 12–26 V power (+DC, −DC), the REL-LORA 100–230 V AC mains power (L, N).
  • W wireless connection ("Wireless connection"), up to 5000 m ("up to 5000 m")

The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.

Trikdis RF-LORA wireless expander moduleTrikdis RF-LORA wireless expander module Trikdis IO-LORA wireless expander moduleTrikdis IO-LORA wireless expander module Trikdis IO8-LORA wireless expander moduleTrikdis IO8-LORA wireless expander module Trikdis PB-LORA wireless panic buttonTrikdis PB-LORA wireless panic button

3.14 Powering up the communicator

To power up the communicator, switch on its power supply. The LEDs must behave as follows:

  • the STA LED is steady green during power-up and flashes green after start-up – the supply voltage is correct;
  • the SIM LED is steady green and from time to time flashes yellow at least 3 times – the green colour shows that the SIM card has successfully registered on the mobile network, and the number of yellow flashes shows the signal strength of the mobile network. The ETH LED is green if the communicator is connected to the local network (LAN).
  • On a 4G network, a signal level of 3 is sufficient (3 yellow flashes of the SIM LED).
  • If the SIM LED flashes yellow fewer times than this, the signal strength of the mobile network is not sufficient. Choose another place for the communicator, move the antenna, or use a more sensitive mobile antenna (section 1.6).
  • If the LEDs light up differently, find the cause using section 1.5 (LEDs).
  • If none of the FireCom's LEDs light up, check the power supply and the wiring.

4. Quick setup with the TrikdisConfig software

This chapter describes the settings with which the FireCom sends the events to the Protegus 2 app (section 4.1) or to the monitoring station (section 4.2). The other settings of the FireCom are in chapter 6.

 All Trikdis devices can be programmed using a common software. The software is called TrikdisConfig and can be downloaded from the manufacturer's website.

After downloading, install the program. If a new version is available each time you start TrikdisConfig, download and install the recommended update!

  1. Download the TrikdisConfig software (with the button above, or on www.trikdis.com type "TrikdisConfig" in the search field), and install it.
  2. Connect the FireCom to the computer with a USB Type-C cable.
  3. Start TrikdisConfig. The software detects the connected device automatically and opens the FireCom's programming window.
  4. Click the Read [F4] button: the software reads and shows the FireCom's current settings. If the software asks for the administrator or installer code, enter the 6-digit code.

While the USB cable is plugged into the Trikdis device (and the other end into the computer), the device switches to programming mode.

  • Normal operation stops,
  • It draws power from the USB cable,
  • After unplugging, it restarts (if powered).

4.1 Setup for the Protegus 2 app

In the SIM group of the System Options page:

TrikdisConfig – **System Options**, **System general** tab, **SIM** group (two fields each: in the picture 1234 in both PIN fields, internet in both APN fields).
Figure 53. TrikdisConfig – System Options, System general tab, SIM group (two fields each: in the picture 1234 in both PIN fields, internet in both APN fields).
  • 1 SIM card PIN – the SIM card's PIN code
  • 2 APN – the mobile internet access point
  1. Enter the SIM card's PIN code (SIM card PIN).
  2. If needed, change the APN field. You can find the APN on the mobile operator's website; "internet" is universal and works in most operators' networks. Operator data for Europe: APN settings – list of European mobile operators.

In the Cloud application group of the Users & Reporting page:

TrikdisConfig – **Users & Reporting**, **Protegus** tab, **Cloud application** group (in the picture **Parallel reporting** is also ticked).
Figure 54. TrikdisConfig – Users & Reporting, Protegus tab, Cloud application group (in the picture Parallel reporting is also ticked).
  • 3 Enable cloud service – switching on the Protegus cloud
  • 4 Cloud Access Code – the cloud access code (123456 by default)
  1. Tick the Enable cloud service checkbox.
  2. If you want users to have to enter the code when they add the system to Protegus 2, change the value of the Cloud Access Code (123456 by default).

On the Settings tab of the Reporting to CMS page:

TrikdisConfig – **Reporting to CMS**, **Settings** tab.
Figure 55. TrikdisConfig – Reporting to CMS, Settings tab.
  • 5 DHCP – automatic network setup
  • 6 Protegus reporting mode – the order of the connection types used towards Protegus 2 (in the picture Main type: Ethernet (LAN), Backup type: SIM, Backup type 2: Disabled)
  1. If a LAN cable is connected to the communicator, tick the DHCP checkbox (automatic registration mode): this way the FireCom reads the network settings (subnet mask, gateway) automatically and gets an IP address.
  2. Here you set how the communicator sends the messages to Protegus 2. The connection types follow each other in order: if the connection fails with the primary connection type, the communicator switches to the next one, and so on. If the message was delivered to Protegus 2 over a backup connection type, after the set time the communicator tries the primary connection type again (Return to Primary).
  3. On the Zones settings tab of the Zones page, tick the Prot. checkbox for the zones whose state changes the users should be notified about in Protegus 2 (section 6.6).
  4. On the Outputs tab of the PGM page, tick the Prot. checkbox for the PGM outputs whose state changes the users should be notified about in Protegus 2 (section 6.7).
  5. On the Events tab of the System events page, tick the Prot. checkbox for the communicator's internal events whose state changes the users should be notified about in Protegus 2 (section 6.9).

At the end of the setup, click the Write [F5] button and unplug the USB cable. Adding the system to the Protegus 2 app: section 5.1.

Chapter 6 covers the other TrikdisConfig settings of the FireCom.

4.2 Setup for the monitoring station

On the System general tab of the System Options page:

TrikdisConfig – **System Options**, **System general** tab.
Figure 56. TrikdisConfig – System Options, System general tab.
  • 1 Object ID – object identifier (0001 in the picture)
  • 2 SIM card PIN – the SIM card's PIN code
  • 3 APN – the mobile internet access point
  1. Enter the object identifier received from the monitoring station (Object ID, account number): 4 characters, 0–9 and A–F. Do not use the identifiers FFFE and FFFF.
  2. Enter the SIM card's PIN code (SIM card PIN).
  3. If needed, change the APN field. You can find the APN on the mobile operator's website; "internet" is universal and works in most operators' networks.

On the Settings tab of the Reporting to CMS page:

TrikdisConfig – **Reporting to CMS**, **Settings** tab.
Figure 57. TrikdisConfig – Reporting to CMS, Settings tab.
  • 4 DHCP – automatic network setup
  • 5 CMS reporting mode – the order of the connection types used towards the monitoring station (in the picture Main type: Ethernet (LAN), Backup type: SIM, Backup type 2: Disabled)
  1. If a LAN cable is connected to the communicator, tick the DHCP checkbox (automatic registration mode): this way the FireCom reads the network settings (subnet mask, gateway) automatically and gets an IP address.
  2. Here you set how the communicator sends the messages to the monitoring station. The connection types follow each other in order: if the connection fails with the primary connection type, the communicator switches to the next one, and so on. If the message was delivered to the monitoring station over a backup connection type, after the set time the communicator tries the primary connection type again (Return to Primary).

On the Reporting tab of the Reporting to CMS page:

TrikdisConfig – **Reporting to CMS**, **Reporting** tab.
Figure 58. TrikdisConfig – Reporting to CMS, Reporting tab.
  • 6 Communication type – the connection type
  • 7 Domain or IP – the receiver's address
  • 8 Port – the receiver's port
  • 9 Protocol – transmission protocol
  • 10 Encryption Key – encryption key (123456 in the picture)
  • 11 Backup channel – the backup channel
  • 12 Parallel channel – the parallel channel (TCP/IP in the picture)
  1. Communication type – select the connection type (TCP or UDP).
  2. Domain or IP – enter the receiver's domain name or IP address.
  3. Port – enter the receiver's network port.
  4. Protocol – select the protocol the device uses to send the messages: TRK (for Trikdis receivers), DC-09_2007 or DC-09_2012 (for universal receivers), TL150 (for Sur-Gard receivers).
  5. Encryption Key – enter the receiver's encryption key.

If you select DC-09 as the transmission protocol, also enter the object, line and receiver numbers in the Settings group of the Reporting to CMS page (section 6.3).

  1. (Recommended) Set up the backup channel (Backup channel).
  2. If the messages must also be sent to the monitoring station's second receiver, set up the parallel channel (Parallel channel).

At the end of the setup, click the Write [F5] button and unplug the USB cable.

Chapter 6 covers the other TrikdisConfig settings of the FireCom.

5. Remote control

The FireCom can be controlled from the Protegus 2 app, by SMS command and by phone call (with the phone's keypad during the call). In the app the users also see the state of the system and receive notifications about system events; by SMS the administrator can also change some of the settings.

5.1 Adding the FireCom to Protegus 2

In Protegus 2 the users see the state of the system and receive notifications about system events. The app is available for phones and in the browser (the download links are below, at creating the system).

Before you add the system

You can add the FireCom to Protegus 2 if:

  1. it has an activated SIM card in it, and you have entered or switched off the PIN code;
  2. the Protegus service is switched on (Users & Reporting → Enable cloud service, sections 4.1 and 6.4; by SMS: CONNECT 123456 PROTEGUS=ON, section 5.2);
  3. its power is switched on (the STA LED flashes green);
  4. it is connected to the network (the SIM LED is steady green and flashes yellow, and/or with a LAN connection the ETH LED is green).

Creating the system in the Protegus 2 application

  1. Download the Protegus 2 application to your phone or open it in a browser
  2. Protegus 2
    Protegus 2 at Play store
    Protegus 2 at App store
    Protegus 2 app in any browser
  3. Register an account if you haven't already.
  4. Log into your account.
  5. On the main page, click the "+" button to create a system
  6. Add new system
  7. Enter the unique identifier of the TRIKDIS device (you can also scan the barcode or QR code with your phone's camera), which you can find
    • On the sticker of the device
    • On the device's cardboard box
    • In the bottom left corner of TrikdisConfig (selectable and copyable format)
  8. Enter the device's unique identifier
  9. Enter the system name and select a time zone
  10. Name and time zone
  11. Your system is created, you can still name the partitions and zones at the next step, but you can do this later anytime.
  12. The system is ready
  13. In the last step, your system's home screen will appear. Wait until the yellow stripe disappears and your system is ready.
  14. Wait until the yellow stripe disappears

With the FireCom, pay attention to the following when adding it:

  1. After Add new system, enter the FireCom's unique identifier (Unique ID), then click the Next button. You can find the identifier on the sticker on the device and on the box; with a USB connection you also see it in the TrikdisConfig status bar (section 6.1).
  2. If the installer has changed the factory value 123456 of the Cloud Access Code, the app asks for the code when you add the system (section 4.1).

5.2 Setup and control by SMS message

1. Change the administrator password. For security, replace the factory administrator SMS password. Send an SMS in this format:

PSW 123456 xxxxxx

Part Meaning
123456 the factory administrator password
xxxxxx the new, 6-character administrator password

2. Allow control for other users. The system can only be controlled by SMS and phone call from the phone numbers on the user list. From the administrator's phone, send an SMS with the phone numbers and names of the other people so that they can also control the system:

SETN xxxxxx PHONEx=+PHONENR#NAME#EMAIL

Part Meaning
xxxxxx the 6-character administrator password
x the user's number on the list (if you enter 1, you hand over your administrator rights to the other user)
PHONENR the user's phone number
NAME the user's name
EMAIL the user's e-mail address

List of SMS commands

Command Data Description
INFO Request for information about the communicator: the reply contains the object name, the partition state, the IMEI number, the mobile network signal strength, the firmware version and the serial number. Example: INFO 123456
RESET Restarts the device. Example: RESET 123456
OUTPUTx ON Switches an output on; "x" is the number of the output. Example: OUTPUT1 123456 ON
OUTPUTx OFF Switches an output off; "x" is the number of the output. Example: OUTPUT1 123456 OFF
OUTPUTx PULSE=ttt Switches an output on for a few seconds: "x" is the number of the OUT output, "ttt" is a three-digit number, the pulse time in seconds. Example: OUTPUT1 123456 PULSE=002
PSW new password Changes the password. Example: PSW 123456 654123
TIME YYYY/MM/DD,12:00:00 Sets the date and time. Example: TIME 123456 2026/05/09,10:02:00
TXTA object name Sets the name of the object. Example: TXTA 123456 House
RDR PhoneNR#SMStext Forwards an SMS to the given number; the phone number must start with "+" and the international country code. Example: RDR 123456 +37061234567#forwarded text
ASKI SMS query about the state of the inputs (IN). Example: ASKI 123456
ASKO SMS query about the state of the outputs (OUT). Example: ASKO 123456
ASKT SMS with the values of all temperature sensors. Example: ASKT 123456
FRS Resets the fire detector output if the Fire sensor reset function is assigned to the OUT output (section 6.7). Example: FRS 123456
SETN PhoneX=PhoneNR#Name#email Adds a phone number, user name and e-mail address for user "x" ("x" is the row of the phone number on the list). The phone number must start with "+" and the international country code; the phone number and the user name are separated by a # sign. Example: SETN 123456 PHONE5=+37061234567#JOHN#jonas@trikdis.lt
SETN PhoneX=DEL Deletes the user's phone number and name from the system. Example: SETN 123456 PHONE5=DEL
UUSD *Uusd code# Sends a USSD code to the operator (the name of the command really is UUSD). Example: UUSD 123456 *245#
CONNECT Protegus=ON Connects to the Protegus cloud service. Example: CONNECT 123456 PROTEGUS=ON
CONNECT Protegus=OFF Disconnects from the Protegus cloud service. Example: CONNECT 123456 PROTEGUS=OFF
CONNECT Code=123456 The code of the Protegus cloud service. Example: CONNECT 123456 CODE=123456
CONNECT IP=0.0.0.0:8000 The TCP IP address and port of the main server's connection channel. Example: CONNECT 123456 IP=0.0.0.0:8000
CONNECT IP=0 Switches off the main channel. Example: CONNECT 123456 IP=0
CONNECT ENC=123456 The TRK encryption key. Example: CONNECT 123456 ENC=123456
CONNECT APN=Internet The APN name. Example: CONNECT 123456 APN=INTERNET
CONNECT USER=user The APN user name. Example: CONNECT 123456 USER=User
CONNECT PSW=password The APN password. Example: CONNECT 123456 PSW=Password

5.3 Controlling the PGM outputs by phone call

If you want to control a PGM output remotely:

  • The user must have the right to control the outputs (OUT) (section 6.4), and the Remote control type must be assigned to the output (OUT) in TrikdisConfig (PGM page, Output definition, section 6.7).
  • Call the number of the FireCom's SIM card. The FireCom answers the call, and you can enter commands with the phone's keypad according to the table.
Keys Function Description
[output]*[state]# controlling the selected output (OUT) Switches the given PGM output. State: 0 – output off; 1 – output on; 2 – off for the pulse time; 3 – on for the pulse time (the pulse time can be set in the TrikdisConfig PGM table, section 6.7). The # marks the end of the command. Examples: switching output 1 on: 1*1#; switching output 1 off: 1*0#; switching output 2 on for the pulse time set in the PGM table: 2*3#
# restarting the command If you made a mistake in the command, press the phone's # key and enter the command again.

6. TrikdisConfig pages

This chapter describes the pages of the TrikdisConfig programming window, in the order in which they follow each other in the menu on the left. Connecting the FireCom with a USB cable: chapter 4; remotely: chapter 7.

6.1 The status bar

After connecting the device and reading it (Read [F4]), the most important device data are shown at the bottom of the window:

Label Meaning
IMEI / Unique ID, on an Ethernet device MAC / Unique ID The device's unique identifier: the IMEI on a device with a SIM card, the MAC address on an Ethernet device. The same is printed on the box and on the back of the device.
Status The current operating status.
Device The device type (model designation). Check that the type of your own device is shown here.
SN Serial number.
BL The bootloader version.
FW The firmware version.
HW The hardware version.
State The connection mode: USB or remote.
Administrator / Installer The access level of the person programming (after the password has been entered).

After making the settings, you write them to the device with the Write [F5] button; with the Open [F8] and Save [F9] buttons you can save the complete set of settings to a file and load it into another device. Save [F9] saves the settings to a settings file, and Open [F8] opens the saved file; you can later load the saved settings into other devices as well, so you can quickly set up several devices with identical settings.

The FireCom's status bar: **Status: Ready**, **BL** 1.02, **FW** 1.07, **State: USB**, **Role: Administrator**; on the left the **IMEI/Unique ID** and serial number (**SN**) fields. For the FireCom, the **Device** field must show the type **FC_xxxx** (FC_E170 in the picture).
Figure 59. The FireCom's status bar: Status: Ready, BL 1.02, FW 1.07, State: USB, Role: Administrator; on the left the IMEI/Unique ID and serial number (SN) fields. For the FireCom, the Device field must show the type FC_xxxx (FC_E170 in the picture).

When you click the Read [F4] button, the software reads and shows the current settings stored on the FireCom. Set the required parameters based on the following page descriptions.

6.2 "System Options" page

The general settings of the device, on three tabs: System general, Groups and Access.

System general tab

TrikdisConfig – **System Options**, **System general** tab: the **General**, **SIM** and **Time settings** groups. In the picture: **Object ID** 0001, **Object name** Fire communicator, **Test period** 1 day 0 hours, **Start test at** 13:30, **Text language** English, suspension after 10 identical events / 10 s, restore after 1 minute, **Call** 2 times, **EOL Type** 10k+10k+5k6, **Communication path test** 1 day; **Time set**: GSM modem, **Daylight saving time** ticked, **Power failure delay** 300 s.
Figure 60. TrikdisConfig – System Options, System general tab: the General, SIM and Time settings groups. In the picture: Object ID 0001, Object name Fire communicator, Test period 1 day 0 hours, Start test at 13:30, Text language English, suspension after 10 identical events / 10 s, restore after 1 minute, Call 2 times, EOL Type 10k+10k+5k6, Communication path test 1 day; Time set: GSM modem, Daylight saving time ticked, Power failure delay 300 s.

General group

  • Object ID – if the events go to the monitoring station, enter the object identifier received from the monitoring station (4-character hexadecimal number, 0–9, A–F). Do not use the identifiers FFFE and FFFF.
  • Object name – the name of the object; this name appears in the SMS messages sent to the users.
  • Test period – when ticked, the FireCom sends a "Test" message at the set interval.
  • Start test at – when ticked, here you set at what time the test messages are sent.
  • Clear Events after reset – when ticked, all unsent event messages are deleted on restart (reset).
  • Text language – the language of the SMS messages: the device uses the specific characters of the selected language in the SMS messages.
  • Suspend event reporting when … same events per … s – suspends event reporting if the given number of identical events repeats within the given number of seconds.
  • Restore event reporting after … min – after this time the suspension of event reporting ends (0–999 minutes).
  • Call – in the event of an event, the FireCom calls the user(s) this many times. If the call is rejected or answered, the FireCom stops calling. One call lasts 20 seconds.
  • EOL Type – the nominal value of the resistors connected to the detectors (EOL – End Of Line; RT + R1 + R2: RT – tamper, R1 – detector 1, R2 – detector 2). The selectable values: section 3.2.
  • Communication path test – the interval after which the communicator checks the backup communication channels: it sends a message over them to the monitoring station. After the messages have been sent, the communicator returns to the primary channel.

SIM group

  • SIM card PIN – the SIM card's PIN code.
  • APN – the name of the mobile operator's mobile internet access point. You must enter it if the event messages go over a mobile data connection (GPRS) to the Protegus 2 app or to the monitoring station. Operator data for Europe: APN settings – list of European mobile operators.
  • Login, Password – the APN user name and password, if the mobile operator requires them.
  • Locked ICCID – if you want the communicator to work only with a specific SIM card, enter the card's ICCID number.
  • Preferred operator – after you enter the mobile operator's code, the communicator connects only to the network of the selected operator. The operator code consists of the MCC (country code) and the MNC (network code).

Time settings group

You can set the time with the Set PC time button. If Disabled is shown in the Time set field, the communicator takes over the computer's time. If a modem or a server is selected in the Time set field, the communicator synchronises its time to it.

  • Time zone (hours) – the time zone of the country (for example +1 for Central European Time).
  • Time set – the server to which the FireCom's internal clock is synchronised. Synchronisation takes place after the communicator is powered up.
  • Daylight saving time – when ticked, the communicator's internal clock switches automatically between summer and winter time.
  • Power failure delay – if the main power supply fails, the notification about the power failure is sent after the given delay. When the supply voltage returns, the notification about the restore is also sent after the given delay.

Groups tab

TrikdisConfig – **System Options**, **Groups** tab: the partition table (in the picture ID 1, **Group name**: Group 1).
Figure 61. TrikdisConfig – System Options, Groups tab: the partition table (in the picture ID 1, Group name: Group 1).

The zones can be assigned to partitions (Zones page, Group column, section 6.6). The name of each partition can be changed; the partition names are shown in Protegus 2.

Access tab

On the Access tab you set the access codes and the installer's permissions.

TrikdisConfig – **System Options**, **Access** tab: the **Access codes** group with the factory codes (**Administrator Code** 123456, **SMS password** 123456, **Installer Code** 654321) and the **Installer permissions** group. In the picture the installer can change the **Object ID** and **SIM card** settings, and besides **Area Settings** the visible pages (**Users & Reporting**, **Modules**, **Zones**, **PGM**, **Reporting to CMS**, **System events**) are also in the **Editable** state.
Figure 62. TrikdisConfig – System Options, Access tab: the Access codes group with the factory codes (Administrator Code 123456, SMS password 123456, Installer Code 654321) and the Installer permissions group. In the picture the installer can change the Object ID and SIM card settings, and besides Area Settings the visible pages (Users & Reporting, Modules, Zones, PGM, Reporting to CMS, System events) are also in the Editable state.

Access codes group

  • Administrator Code – full access to the settings (123456 by default).
  • SMS password – password for remote control and programming by SMS (123456 by default).
  • Installer Code – limited access for changing the settings (654321 by default).

If the factory administrator code (123456) is set, after you press Read [F4] the software immediately shows the device's current operating parameters without asking for a code.

Installer permissions group – here the administrator sets which parameters the installer can change.

For security, change the factory codes. You can also change the SMS password by SMS (PSW, section 5.2).

6.3 "Reporting to CMS" page

The FireCom sends the messages to the monitoring station over the internet (IP). A backup channel can be assigned to the primary channel: the device uses it if the connection on the primary channel is lost. The page has two tabs: Reporting and Settings.

Reporting tab

TrikdisConfig – **Reporting to CMS**, **Reporting** tab: the **Primary channel**, **Backup channel**, **Parallel channel** and **Parallel backup channel** groups. In the picture the **Communication type** field of the primary and backup channels is **Disabled**, that of the parallel and parallel backup channels is **TCP/IP**; on all four channels **Port** 0, **Protocol** TRK, **Encryption Key** 123456, the **Domain or IP** fields are empty.
Figure 63. TrikdisConfig – Reporting to CMS, Reporting tab: the Primary channel, Backup channel, Parallel channel and Parallel backup channel groups. In the picture the Communication type field of the primary and backup channels is Disabled, that of the parallel and parallel backup channels is TCP/IP; on all four channels Port 0, Protocol TRK, Encryption Key 123456, the Domain or IP fields are empty.

The messages sent to the monitoring station are encoded and password-protected. To receive the messages and pass them on to the monitoring software, a Trikdis receiver is needed:

  • For IP messages: the IPcom receiver software (Windows or Linux), the RL14 IP/SMS hardware receiver or the RM14 multichannel receiver.
Trikdis IPcom v5 Windows software receiverTrikdis IPcom v5 Windows software receiver Trikdis IPcom v5 Linux software receiverTrikdis IPcom v5 Linux software receiver

Primary channel group – and in the same way the Parallel channel

  • Communication type – the connection method with the monitoring station's receiver.
  • Domain or IP – the receiver's domain name or IP address.
  • Port – the receiver's network port.
  • Protocol – the encoding used for the events: TRK (for Trikdis receivers), DC-09_2007 or DC-09_2012 (for universal receivers; when you select the SIA DC protocol, the SIA-DCS message format can also be selected), TL150 (for Sur-Gard receivers).
  • Encryption Key – 6-digit encryption key; the communicator's encryption key must match the receiver's.

If you also enter the parameters of the parallel channel (Parallel channel), the messages go over both channels at the same time. The two channels cannot be set to the same receiver.

Backup channel group – and in the same way the Parallel backup channel. Switch on the backup channel so that the messages go over the backup channel if the connection is lost. Its settings are the same as above.

Settings tab

TrikdisConfig – **Reporting to CMS**, **Settings** tab. In the picture: **Return to Primary after** 5 minutes, **IP Ping period** switched on at 60 s, **Backup reporting after** 3 attempts, **DNS1** 8.8.8.8, **DNS2** 1.1.1.1; **DHCP** ticked; towards both the monitoring station (**CMS**) and Protegus **Main type**: Ethernet (LAN), **Backup type**: SIM, **Backup type 2**: Disabled.
Figure 64. TrikdisConfig – Reporting to CMS, Settings tab. In the picture: Return to Primary after 5 minutes, IP Ping period switched on at 60 s, Backup reporting after 3 attempts, DNS1 8.8.8.8, DNS2 1.1.1.1; DHCP ticked; towards both the monitoring station (CMS) and Protegus Main type: Ethernet (LAN), Backup type: SIM, Backup type 2: Disabled.

Settings group

  • Return to Primary after – after this time the FireCom tries to return to the primary channel (Primary channel).
  • IP PING period – the interval at which internal PING signals checking the connection are sent. The PING signals are sent only on an IP channel; the receiver does not pass them on to the monitoring software, so they do not load it. The software is notified only if the receiver gets no PING from the device for the set time.
  • Backup reporting after – after how many unsuccessful sending attempts the FireCom sends on the backup channel (Backup channel): if the message is still not sent on the primary channel (Primary channel) after this many attempts, the device sends it on the backup channel.
  • DNS1, DNS2 – the DNS servers (Domain Name System) that translate the domain name into an IP address. They are needed if you entered a domain name (and not an IP address) in the channel's Domain or IP field. By default, Google's DNS servers.

The PING interval

By default the receiver sends a "Connection lost" message to the monitoring software if it gets no PING for three times the communicator's PING interval: for example, with a 3-minute IP PING period, after 9 minutes. The PING messages also keep the connection between the device and the receiver active – the active connection is needed for remote setup and control. We recommend setting the PING interval to no more than 5 minutes.

The fields below are visible only if you selected the DC-09_2007 or DC-09_2012 protocol in the channel's Protocol field:

  • Object ID in SIA DC-09 – the object number; with the DC-09 protocol this number is put into the messages. Enter the 3–16-character hexadecimal number received from the monitoring station.
  • SIA DC-09 receiver No. – the receiver number.
  • SIA DC-09 line No. – the line number in the receiver.
  • Local time in SIA – when ticked, the messages sent to the monitoring station contain the time set in the module.

Reporting mode group

Here you set how the communicator communicates on the monitoring station channels and with Protegus 2. The connection types follow each other in order: if the communicator cannot connect with the Main type connection type, it switches to the Backup type, and so on. If the message was delivered to the monitoring station over a backup connection type, after the given time the communicator tries the primary connection type again (Return to main).

  • Main type – the primary connection type (SIM or Ethernet (LAN)) towards the monitoring station receiver and Protegus 2.
  • Backup type – the backup connection type (SIM or Ethernet (LAN)) towards the monitoring station receiver and Protegus 2.
  • Backup type 2 – the second backup connection type (SIM or Ethernet (LAN)) towards the monitoring station receiver and Protegus 2.
  • Dual path for CMS – dual path mode: CMS1 works over LAN, CMS2 over SIM. The two channels and communication paths work in parallel.
  • Return to main (both channel) – after this many minutes the FireCom tries to return to the primary channel if it has been working on a backup channel.

LAN network parameters group

  • DHCP mode – the method of registering on the local network (LAN) (manual or automatic). When ticked (automatic registration mode), the FireCom reads the network settings (subnet mask, gateway) automatically and gets an IP address automatically.
  • Static IP – static IP address in manual mode.
  • Subnet mask – subnet mask in manual mode.
  • Default gateway – default gateway in manual mode.
  • LAN Trouble indication – when ticked, the communicator's LED lights up if the LAN connection is lost.

SIM parameters group

  • Disable indication of the absence of a SIM card – when ticked, the FireCom does not indicate if there is no SIM card in it.
  • Use dial and SMS when working over internet module – when ticked, the communicator can also be controlled by call and SMS. If it is not ticked and there is a LAN network, SMS and calls are not used. If it is not ticked and there is no LAN network, the FireCom can still be controlled by call and SMS, and it sends SMS messages to the user.
  • Disable the use of SIM card mobile data – when ticked, the FireCom does not use the SIM card's mobile data connection: data is sent only over LAN. If the LAN network is temporarily unavailable, the FireCom stores the data in its memory and sends it over LAN once the LAN is back.

6.4 "Users & Reporting" page

The settings of the users, the Protegus cloud and the SMS replies, on three tabs: Users, Protegus and SMS answer texts. Setting up SMS messages and calls about the events of the fire alarm control panel (SMS for Panel events tab): section 3.6.

Users tab

TrikdisConfig – **Users & Reporting**, **Users** tab, with sample data: in the first row (1A) of the **Users & Reporting to User** table the **Name**, **Tel number** and **Email** fields are filled in, the **PGM**, **ACK** and **FWD** checkboxes are ticked; the other visible rows are empty.
Figure 65. TrikdisConfig – Users & Reporting, Users tab, with sample data: in the first row (1A) of the Users & Reporting to User table the Name, Tel number and Email fields are filled in, the PGM, ACK and FWD checkboxes are ticked; the other visible rows are empty.

Users & Reporting to User group

  • ID – the user's number on the list.
  • Name – the user's name; this name appears in the event SMS messages and in the app.
  • Tel number – the user's phone number to which the SMS messages are sent; enter it starting with the international country code (+…). The first 8 phone numbers receive messages and calls about the events.
  • E-mail – the user's e-mail address: the user receives the invitation to Protegus 2 at this address, so that they can control the system.
  • PGM – when ticked, the user can control the outputs remotely (by call, by SMS).
  • ACK – when ticked, the FireCom sends a reply SMS to the user after every SMS command received (the text of the replies: SMS answer texts tab).
  • FWD – when ticked, the FireCom forwards to the user the SMS messages arriving from numbers outside the system (for example the SIM card's balance notifications or advertising messages).

Protegus tab

TrikdisConfig – **Users & Reporting**, **Protegus** tab: in the **Cloud application** group **Enable cloud service** and **Parallel reporting** are ticked, **Cloud Access Code** 123456.
Figure 66. TrikdisConfig – Users & Reporting, Protegus tab: in the Cloud application group Enable cloud service and Parallel reporting are ticked, Cloud Access Code 123456.

Cloud application group

  • Enable cloud service – switches on the Protegus 2 service: this way the FireCom exchanges data with the Protegus 2 app and can also be set up remotely with TrikdisConfig (chapter 7).
  • Parallel reporting – parallel reporting: the messages go at the same time over the primary channel (Primary channel) and to Protegus 2.
  • Cloud Access Code – 6-digit code for logging in to Protegus 2 (123456 by default).

SMS answer texts tab

TrikdisConfig – **Users & Reporting**, **SMS answer texts** tab: **Command done**, **Wrong password**, **Wrong data**, **Wrong command**; on a zone alarm (**Zone alarm**) "Alarm!!", on a zone restore (**Zone restore**) "Alarm restored", when the output is switched on (**Output ON**) "OUT ON", when it is switched off (**Output OFF**) "OUT OFF".
Figure 67. TrikdisConfig – Users & Reporting, SMS answer texts tab: Command done, Wrong password, Wrong data, Wrong command; on a zone alarm (Zone alarm) "Alarm!!", on a zone restore (Zone restore) "Alarm restored", when the output is switched on (Output ON) "OUT ON", when it is switched off (Output OFF) "OUT OFF".

In the SMS text column you can edit the text of the replies sent to SMS commands. The texts of the SMS messages sent when the inputs and outputs are activated are also here.

6.5 "Modules" page

The settings of the expansion modules connected to the RS485 bus and of the fire alarm control panel connected to the RS485 2 bus.

RS485 modules tab

TrikdisConfig – **Modules**, **RS485 modules** tab: the **Module** list opened (**Not available**, iO-8, iO-MO, iO-LORA and iO8-LORA expanders, PB-LORA panic button, REL-LORA expander); the columns of the table: **ID**, **Module**, **Serial No.**, **Name**, **Firmware version**.
Figure 68. TrikdisConfig – Modules, RS485 modules tab: the Module list opened (Not available, iO-8, iO-MO, iO-LORA and iO8-LORA expanders, PB-LORA panic button, REL-LORA expander); the columns of the table: ID, Module, Serial No., Name, Firmware version.

RS485 modules group

  • ID – the module's number on the list.
  • Module – the module used, from the module list: iO-8, iO-MO, iO-LORA, iO8-LORA, PB-LORA, REL-LORA (wiring: section 3.13).
  • Serial No. – mandatory, 6-digit number; you can find it on the module's enclosure and packaging.
  • Name – the name of the module (any).
  • Firmware version – the module's firmware version; it appears when the FireCom finds the connected module.

RS485 2 interface group

TrikdisConfig – **Modules**, **RS485 2 interface** group: the **Interface type** list opened (**Disabled**, **ESPA 4.4.4**, **NSC solution**, **INIM smartline**, **C-TEC Cast ZFP**, **Polon-Alfa 3000**).
Figure 69. TrikdisConfig – Modules, RS485 2 interface group: the Interface type list opened (Disabled, ESPA 4.4.4, NSC solution, INIM smartline, C-TEC Cast ZFP, Polon-Alfa 3000).

A fire alarm control panel can be connected to the FireCom's RS485 2 bus: one with the ESPA 4.4.4 protocol, NSC Solution, INIM Smartline, C-TEC Cast ZFP or Polon-Alfa 3000. Sections 3.5–3.9 describe the wiring and setup of the panels.

6.6 "Zones" page

The settings of the zones (inputs), on three tabs: Zones settings, SMS & Call reporting and Zone's codes.

Zones settings tab

TrikdisConfig – **Zones**, **Zones settings** tab: in the picture zones 1–5 on the **FC 1 I/O** … **FC 5 I/O** inputs, **Group 1**, **EOL** type, 800 ms delay, **CMS** and **Prot.** checkboxes ticked.
Figure 70. TrikdisConfig – Zones, Zones settings tab: in the picture zones 1–5 on the FC 1 I/O … FC 5 I/O inputs, Group 1, EOL type, 800 ms delay, CMS and Prot. checkboxes ticked.
  • Zone No – the zone's number on the list.
  • Name – the zone's name; this name appears in the SMS messages and in the app.
  • Input – which input (IN) of the FireCom or of the expansion module belongs to the zone.
  • Group – assigning the zone to a partition (the partition names: section 6.2, Groups tab).
  • Type – the type of the circuit connected to the zone's input: NC – normally closed; NO – normally open; EOL – with an end-of-line resistor; EOL_T – with an end-of-line resistor and tamper monitoring; ATZ – two-zone, normally closed circuit with end-of-line resistors, without tamper monitoring (to use it, select the second ATZ zone in the input list); ATZ_T – two-zone, normally closed circuit with end-of-line resistors, with tamper monitoring (to use it, select the second ATZ zone in the input list). The wiring diagrams: section 3.2.
  • CMS – when ticked, messages about the zone's events go to the monitoring station.
  • Prot. – when ticked, notifications about the zone's events go to the Protegus 2 app.
  • Delay – the reaction time of the input (IN) in milliseconds.

SMS & Call reporting tab

This tab appears only if you have entered at least one user phone number on the Users & Reporting page.

TrikdisConfig – **Zones**, **SMS & Call reporting** tab: in the **User 1** table one **Event** and one **Restore** row per zone, with **SMS** and **Call** columns (the visible checkboxes are empty in the picture).
Figure 71. TrikdisConfig – Zones, SMS & Call reporting tab: in the User 1 table one Event and one Restore row per zone, with SMS and Call columns (the visible checkboxes are empty in the picture).
  • Zn – the zone number with the event's keyword: Event or Restore.
  • User SMS/Call – for each zone event you can select whether the user receives an SMS and/or a call.

Zone's codes tab

TrikdisConfig – **Zones**, **Zone's codes** tab: the alarm (**E/R**: E, **CID** 110, **SIA** TA, **Group** 1, **Zone** 001) and the restore (**E/R**: R, **CID** 110, **SIA** TR) of zone 1 are switched on; for the visible zones 2–5 the SIA code of the alarm is FA, that of the restore is FH.
Figure 72. TrikdisConfig – Zones, Zone's codes tab: the alarm (E/R: E, CID 110, SIA TA, Group 1, Zone 001) and the restore (E/R: R, CID 110, SIA TR) of zone 1 are switched on; for the visible zones 2–5 the SIA code of the alarm is FA, that of the restore is FH.

When the zone is violated, the communicator sends an event message. A Contact ID (SIA) code belongs to the input; this is sent to the monitoring station and to Protegus 2.

  • Enable – messages go to the monitoring station and to Protegus 2 from the ticked event fields.
  • E/R – which event type is sent when the input is activated: Event (E) or Restore (R).
  • CID – the event code; enter it, or leave the factory value.
  • SIA – the SIA event codes.
  • Group – the partition number sent when the event occurs.
  • Zone – the zone number sent when the event occurs.

6.7 "PGM" page

The settings of the PGM outputs, on four tabs: Outputs, Set Action, Scheduler and SMS & Call reporting.

Outputs tab

TrikdisConfig – **PGM**, **Outputs** tab: PGM 1, 2 and 3 on the **RELAY 1**, **2** and **3** outputs, PGM 4 switched off (**Disable**); in all four visible rows **Remote Control** output definition and 20 s pulse time, the **CMS** and **Prot.** checkboxes empty.
Figure 73. TrikdisConfig – PGM, Outputs tab: PGM 1, 2 and 3 on the RELAY 1, 2 and 3 outputs, PGM 4 switched off (Disable); in all four visible rows Remote Control output definition and 20 s pulse time, the CMS and Prot. checkboxes empty.
  • PGM No – the PGM output's number on the list.
  • Name – the name of the PGM output.
  • PGM output – the output (OUT) assigned to the PGM: that of the FireCom or of an external device.
  • Output definition – the operating mode of the output (OUT) (Remote Control in the picture).
  • Pulse time, s – how long the output (OUT) stays on, 0–9999 seconds.
  • CMS – when ticked, messages about the selected events go to the monitoring station.
  • Prot. – when ticked, notifications about the output's events go to the Protegus 2 app.

Set Action tab

TrikdisConfig – **PGM**, **Set Action** tab: in the visible rows the **Enable** checkbox is empty, **PGM No.**: N/A, **Action**: PGM OFF, **Pulse Time** 0 s, **Factor**: SMS received, **Factor No.** and **Start when**: N/A, **Set value**: SMS text.
Figure 74. TrikdisConfig – PGM, Set Action tab: in the visible rows the Enable checkbox is empty, PGM No.: N/A, Action: PGM OFF, Pulse Time 0 s, Factor: SMS received, Factor No. and Start when: N/A, Set value: SMS text.
  • ID – the output's number on the list.
  • Enable – switches on the PGM operating algorithm.
  • PGM No. – the output (OUT) that the communicator controls when the event described in the Factor, Factor No., Start when and Set value columns occurs.
  • Action – the action:
    • PGM OFF – the state of the output (OUT): off ("Off").
    • PGM ON – the state of the output (OUT): on ("On").
    • Pulse OFF – the initial state of the output (OUT) is on ("On"); after the command it switches off ("Off") for the pulse time (Pulse time), then automatically returns to the initial, on state.
    • Pulse ON – the initial state of the output (OUT) is off ("Off"); after the command it switches on ("On") for the pulse time (Pulse time), then automatically returns to the initial, off state.
  • Pulse time, s – the pulse time, 0–9999 seconds.
  • Factor / Factor No. – which event switches the output (OUT) on: a zone (Zone), the arrival of an SMS (SMS received) or a zone tamper (Zone tamper).
  • Start when – an additional condition for switching the output (OUT) on, depending on the Factor event.
  • Set value – depending on the condition selected in the Factor column, here you can enter a value (the text of the received SMS). If the communicator recognises this value, it performs the action selected in the Action column. You can structure the SMS text with % signs: the % signs separate the keyword that changes the output state from the whole received SMS.
Pattern Meaning Example
%…..% a part of the received SMS text must match the text written between the % signs %hoUSe% – the SMS must contain the text "hoUSe"; for example VacationhoUSe25864
…..% the beginning of the received SMS must match the text written up to the % sign hoUSe% – the SMS must start with the text "hoUSe"; for example hoUSeddss
%….. the end of the received SMS must match the text written after the % sign %hoUSe – the SMS must end with the text "hoUSe"; for example 1144hoUSe

The SMS text is case-sensitive.

Scheduler tab

TrikdisConfig – **PGM**, **Scheduler** tab: the **Start time** and **Stop time** fields of the scheduler table, both with checkboxes from Monday to Sunday (00:00 and empty checkboxes in the picture).
Figure 75. TrikdisConfig – PGM, Scheduler tab: the Start time and Stop time fields of the scheduler table, both with checkboxes from Monday to Sunday (00:00 and empty checkboxes in the picture).
  • ID – the schedule's number on the list.
  • Enable – switches on the schedule.
  • Start time – when the output (OUT) switches on – the start of the schedule.
  • Stop time – when the output (OUT) switches off – the end of the schedule.
  • Mon – Sun – the days of the week on which the output (OUT) must switch on or off.

SMS & Call reporting tab

This tab appears only if you have entered at least one user phone number on the Users & Reporting page. These settings can apply only to the first 8 users.

TrikdisConfig – **PGM**, **SMS & Call reporting** tab: the **Event** and **Restore** rows of PGM 1, 2 and 3, with empty **SMS** and **Call** checkboxes in the **User 1** column.
Figure 76. TrikdisConfig – PGM, SMS & Call reporting tab: the Event and Restore rows of PGM 1, 2 and 3, with empty SMS and Call checkboxes in the User 1 column.
  • PGM – the number of the output (OUT) and the event type: Event – the output switches on; Restore – the output switches off.
  • User SMS/Call – you can select which users receive an SMS and/or a call when the output (OUT) switches on and off.

6.8 "Sensors" page

The settings of the temperature sensors (wiring: section 3.10).

TrikdisConfig – **Sensors**: eight sensor rows (**Module type**: Disable, **Sensor 1** … **Sensor 8**, **Max** 30, **Min** 2, **High** and **Low** ticked, **Delay** 0 minutes); the **Sensor type** list opened: **Dallas 1-Wire** and **Humidity & Temperature (AM23xx series)**.
Figure 77. TrikdisConfig – Sensors: eight sensor rows (Module type: Disable, Sensor 1 … Sensor 8, Max 30, Min 2, High and Low ticked, Delay 0 minutes); the Sensor type list opened: Dallas 1-Wire and Humidity & Temperature (AM23xx series).
  • ID – the temperature sensor's number on the list.
  • Module type – the temperature sensor assigned to the row (ID).
  • Serial No. – the sensor's serial number; the communicator reads it out.
  • Sensor name – the name of the sensor.
  • Max – if the temperature is higher than this, an event message is generated; for this the High checkbox must be ticked.
  • Min – if the temperature is lower than this, an event message is generated; for this the Low checkbox must be ticked.
  • Delay – the event is sent if the value measured by the sensor crosses the Max or Min value within the set time. Enter the time in minutes.
  • Sensor type – the type of the connected temperature sensor: Dallas 1Wire – up to 8 such sensors can be connected, and the communicator assigns them automatically; Humidity & Temperature – one AM2301 temperature and humidity sensor can be connected; if you use it, it must be assigned manually in the Module type column.

6.9 "System events" page

The settings of the communicator's own (system) events, on two tabs: Events and SMS & Call reporting.

Events tab

TrikdisConfig – **System events**, **Events** tab: low battery voltage (**Low Battery**, CID 302), periodic test (**Periodic test**, 602), missing battery (**Battery missing**, 311), RS485 fault (**RS485 fault**, 333), high temperature (**High temperature**, 158), low temperature (**Low temperature**, 159) and lost temperature sensor (**Temp. sensor lost**, 380), with the **Enable**, **CMS** and **Prot.** checkboxes ticked; next to them the fields of the SMS event and restore texts.
Figure 78. TrikdisConfig – System events, Events tab: low battery voltage (Low Battery, CID 302), periodic test (Periodic test, 602), missing battery (Battery missing, 311), RS485 fault (RS485 fault, 333), high temperature (High temperature, 158), low temperature (Low temperature, 159) and lost temperature sensor (Temp. sensor lost, 380), with the Enable, CMS and Prot. checkboxes ticked; next to them the fields of the SMS event and restore texts.
  • ID – the event's number on the list.
  • Event name – the name of the event.
  • Enable – switches on monitoring of the event.
  • CMS – messages about the selected events go to the monitoring station.
  • Prot. – notifications about the selected events go to the Protegus 2 app.
  • CID Code – the Contact ID code of the event.
  • SMS event text – the SMS text of the event.
  • SMS restore text – the SMS text of the restore.

SMS & Call reporting tab

This tab appears only if you have entered at least one user phone number on the Users & Reporting page.

TrikdisConfig – **System events**, **SMS & Call reporting** tab: in the **Event SMS text** column for example Battery low, Battery restore, Periodic test, Battery missing; in the **User 1** column empty **SMS** and **Call** checkboxes.
Figure 79. TrikdisConfig – System events, SMS & Call reporting tab: in the Event SMS text column for example Battery low, Battery restore, Periodic test, Battery missing; in the User 1 column empty SMS and Call checkboxes.
  • ID – the event's number and keyword (Event, Restore).
  • Event SMS text – the text of the event that goes into the SMS message.
  • User SMS/Call – for each event you can select whether the user receives an SMS and/or a call.

6.10 "Events Log" page

Here you can read out and clear the device's event log.

TrikdisConfig – **Events Log**: the **Read Log** and **Clear Log** buttons; in the table the event's number (**Event No.**), time (**Time**), **CID** code and description (**Event definition**) – in the picture the first entry is the main power failure (**Main power failure**, CID 301:00:000).
Figure 80. TrikdisConfig – Events Log: the Read Log and Clear Log buttons; in the table the event's number (Event No.), time (Time), CID code and description (Event definition) – in the picture the first entry is the main power failure (Main power failure, CID 301:00:000).
  • Read Log – the button reads the event log from the device's memory.
  • Clear Log – the button deletes the log entries from the device's memory.
  • The table shows the event's number (Event No.), time (Time), CID code and description (Event definition). The log shows up to 1000 events stored in the FireCom's memory.

6.11 Restoring the factory settings

To restore the FireCom's factory settings, click the Restore button in TrikdisConfig.

TrikdisConfig – the factory settings (**Default settings**) area, with the **Restore** button framed in red; the status bar shows **Ready**, **State: USB**, **Role: Administrator**.
Figure 81. TrikdisConfig – the factory settings (Default settings) area, with the Restore button framed in red; the status bar shows Ready, State: USB, Role: Administrator.

If you may need the current settings later, save them to a file with the Save [F9] button before restoring (section 6.1).

7. Remote programming

You can also read and change the FireCom's settings remotely with TrikdisConfig, through the Protegus cloud – you do not need to go to the site.

Conditions for remote programming

Remote setup works only if the FireCom:

  1. has an activated SIM card in it, and you have entered or switched off the PIN code;
  2. has the Protegus service switched on (Users & Reporting → Enable cloud service, section 6.4);
  3. has its power switched on (the STA LED flashes green);
  4. is connected to the network (the SIM LED is steady green and flashes yellow, and/or with a LAN connection the ETH LED is green).

If the SIM or the DAT LED is steady yellow, the device cannot connect to the mobile network and/or to Protegus 2.

  1. Start TrikdisConfig on the computer.
  2. In the Remote access area, enter the FireCom's unique identifier (Unique ID) in the Unique ID field. You can find this number on the back of the device and on its packaging.
TrikdisConfig – the **Remote access** area of the start window: the empty **Unique ID** field and the **Configure** button framed in red; next to them the **System Name** field and the **Control** button.
Figure 82. TrikdisConfig – the Remote access area of the start window: the empty Unique ID field and the Configure button framed in red; next to them the System Name field and the Control button.
  1. (Optional) In the System Name field, enter a name for the device (for example the name of the object).
  2. Click the Configure button.
  3. In the window that opens, click the Read [F4] button. If the software asks for it, enter the administrator or installer code.
  4. At the end of the setup, click the Write [F5] button. When you have finished with TrikdisConfig, click the Disconnect button.

8. Testing the operation

At the end of the setup and installation, test the whole system:

  1. To check an input, activate (violate) the input. Check whether the event has arrived at the monitoring station and/or in the Protegus 2 app.
  2. To check the outputs, switch them on remotely and check that they work. Make sure that the events have arrived at the monitoring station and/or in the Protegus 2 app.
  3. Carry out a fire alarm test, and check that the monitoring station receives the events correctly.

The DAT LED (DATA on the front) shows whether the messages have been sent: if it is off, all event messages have been sent; with a steady green light a message is being sent; if DAT is steady yellow, there are unsent event messages in the buffer (section 1.5).

You can also query the communicator's data, the state of the inputs and outputs and the values of the temperature sensors by SMS: INFO 123456, ASKI 123456, ASKO 123456, ASKT 123456 (replace 123456 with your own SMS password; section 5.2).

9. Firmware update

When you connect the FireCom to TrikdisConfig and newer firmware is available, the software offers the update by itself – for this the computer must be online. An antivirus program, a firewall or strict internet access settings can block the automatic update; in that case you must change the antivirus program's settings.

You can update the firmware yourself – to a newer version and, if necessary, to an older one as well. All device settings remain unchanged after the update.

  1. Start the TrikdisConfig software and connect the device with a USB cable, or open its programming remotely.
  2. If newer firmware is available, the software offers to download it – accept it.
  3. Select the Firmware page and click the Open firmware button. Select the firmware file.
  4. Press the Update [F12] button, wait for the update to finish, then click OK in the pop-up window. Do not unplug the cable or interrupt the connection in the meantime.

The firmware files are in the TrikdisConfig installation folder, inside the Firmwares subfolder, in the folder named after the device. If there is no such folder, either there is no update for it or the TrikdisConfig software itself needs to be updated. The latest files can also be downloaded as a registered user from the device's page on the manufacturer's website.

Connect the FireCom to the computer with a USB Type-C cable, or log in remotely (chapter 7).

TrikdisConfig – FireCom, **Firmware** page: the **Open firmware file** field, the **Open firmware** button, the **Update [F12]** button and the progress bar.
Figure 83. TrikdisConfig – FireCom, Firmware page: the Open firmware file field, the Open firmware button, the Update [F12] button and the progress bar.

10. Troubleshooting and frequently asked questions

If the communicator does not do what you expect, first look at the LEDs (section 1.5), then at the points below.

The STA LED (TROUBLE on the front) flashes red – what does the number of flashes mean?

The number of flashes is the cause of the fault: 1 – no SIM card inserted; 2 – the SIM card's PIN code is wrong (System Options → SIM card PIN, section 6.2); 3 – cannot connect to the mobile network; 4 – cannot connect to the IP receiver on the primary channel (Reporting to CMS, section 6.3); 5 – cannot connect to the IP receiver on the backup channel; 6 – no DC supply voltage (section 2.1); 7 – AUX output fault (overcurrent or overvoltage); 8 – battery fault (section 2.2); 9 – the LAN cable is not connected; 10 – DHCP error on the local network (LAN network parameters, section 6.3).

The FPS LED (POWER on the front) flashes green – what is wrong?

1 green flash: no mains (AC) supply voltage. 2 green flashes: the voltage of the backup power supply (battery) is not sufficient (section 2.2). If the LED is steady green, there is no problem with the power supply (section 1.5).

How many yellow flashes are needed on the SIM LED?

The number of yellow flashes shows the signal strength of the mobile network: on a 4G network, 3 flashes are already sufficient. If you count fewer yellow flashes than this, the signal strength is not sufficient: choose another place for the communicator, move the antenna, or use a more sensitive mobile antenna (sections 1.6 and 3.14). If none of the FireCom's LEDs light up, check the power supply and the wiring.

The ETH LED flashes green

The LAN cable is not connected, or there is a DHCP error (section 1.5). Check the cable and the router. For automatic address assignment, DHCP mode must be ticked; for manual setup, fill in the Static IP, Subnet mask and Default gateway fields (Reporting to CMS → Settings, LAN network parameters, section 6.3). What the network must provide: section 3.1.

Protegus 2 cannot find the communicator
  • Check the conditions for adding it: activated SIM card, PIN code entered or switched off, Protegus service switched on (Users & Reporting → Enable cloud service, section 6.4), STA flashing green, and the SIM LED steady green and flashing yellow and/or the ETH LED green (section 5.1).
  • If the SIM or the DAT LED is steady yellow, the device cannot connect to the mobile network and/or to Protegus 2 (chapter 7). Check the APN setting (section 6.2).
  • If the Cloud Access Code is not the factory 123456, enter the correct code when adding the system (section 4.1).
I cannot control the outputs by call or SMS
  • Control by SMS and call is only possible from the phone numbers on the user list (section 5.2).
  • The user must have the right to control the outputs (PGM checkbox, section 6.4), and the Remote control definition must be assigned to the output (Output definition, section 6.7).
  • Check the Use dial and SMS when working over internet module checkbox (section 6.3): if it is not ticked and there is a LAN network, calls and SMS are not used.
I get no reply to my SMS commands

For the reply SMS, the ACK checkbox must be ticked for the user (Users & Reporting, section 6.4). You can edit the text of the replies on the SMS answer texts tab.

Can the data go over the local network (LAN) only?

Yes. If you tick the Disable the use of SIM card mobile data checkbox, the FireCom does not use the SIM card's mobile data connection: the data goes over LAN only. If the LAN is temporarily unavailable, the communicator stores the data in its memory and sends it once the LAN is back. If there is no SIM card in the communicator, you can switch off the indication of its absence with the Disable indication of the absence of a SIM card checkbox (section 6.3).

How many smoke detectors can be connected to the FLOOP terminal?

Up to 8 two-wire fire detectors whose alarm current is greater than 10 mA. A 2.2 kΩ end-of-line resistor is needed after the last detector, and on the Zones page the FC Fire sensor (FLOOP input) input must be selected as the zone's input (sections 3.3 and 6.6). If you connect the detectors to an IO input, the wiring diagrams are in the same place.

What kind of temperature sensors, and how many, can be connected?

Up to 8 Maxim® / Dallas® DS18S20 or DS18B20 temperature sensors, or 1 AM2301 humidity and temperature sensor. The communicator assigns the Dallas sensors automatically; the AM2301 must be assigned manually on the Sensors page (sections 3.10 and 6.8). You can also query the values by SMS: ASKT (section 5.2).

What battery is needed?

A 12 V, 4 Ah or 7 Ah lead-acid battery (sections 1.2 and 2.1). According to the EN 54 standard, the battery must charge to 80 % of its capacity within 24 hours and reach the rest within the following 48 hours (section 3.1). At 11.5 V a Low Battery message is sent, below 9.5 V the battery is disconnected (section 2.2).

How does the fire alarm control panel know that the message has reached the monitoring station?

According to the EN 54 standard, the panel must know about a fault in the connection to the monitoring station and about the successful reception of the messages. For this, two PGM outputs of the communicator must be connected to the dedicated inputs of the panel: the Relay1 output set to CMS fail switches on when the communication channel is interrupted, and the Relay2 output set to ACK received switches on for 5 seconds when the message has reached the monitoring station (section 3.12).

INIM Smartline: what should I watch out for?

The panel must be set to slave mode in the SmartLeague software. If repeaters are connected to the panel, the FireCom cannot be connected on the RS485 bus; and if the FireCom is connected to the panel's RS485 bus, the iO expansion modules are not supported (section 3.7).

NSC Solution: the panel does not see the communicator

After setting up the FireCom, the modules connected to the RS485 bus must be searched for (scanned) on the panel (SCAN RS485, section 3.6). The NSC slave address must not be the same as the address of the modules connected to the panel.

11. Safety instructions

Attention!

Electricity can be dangerous and may cause personal injury or DEATH, as well as other financial loss or damage if not used or installed properly.

Installation involves working with electrical equipment, and it should be executed in accordance with current regulations!

Warranty validation requires the device to be installed by a qualified person following the installation regulations for electrical equipment and adhering to the current regulations for the safe operation of electrical equipment.

  • The communicator may only be installed and maintained by a qualified person.
  • Read this manual carefully before installation to avoid mistakes that can lead to malfunction or even damage to the equipment.
  • Disconnect the power supply before every electrical connection.
  • Changes, upgrades or repairs not authorized by the manufacturer void the warranty.
  • Follow local waste disposal regulations: do not throw the device and its parts in household waste – hand in the discarded device as electronic waste.

See also