G17F fire communicator – installation and programming manual
Installation and programming manual for the Trikdis G17F cellular fire communicator (EN 54-21): wiring to the outputs or to the RS485 bus of the fire alarm control panel (ESPA 4.4.4, NSC Solution, INIM Smartline, C-TEC Cast ZFP), setup in TrikdisConfig, monitoring station, Protegus 2, control by SMS and phone call.
- 67 min read
1. Overview
The G17F is a fire communicator that forwards the events of any fire detection unit or fire alarm control panel over the mobile network. If an input (zone) is triggered, i.e. a fire alarm comes in, the event is forwarded to the configured destinations, for example to the fire brigade and to the monitoring station. In addition, the owner is also notified about the event in the Protegus 2 mobile and web app.
The G17F forwards the messages of the fire alarm control panel over the mobile network. How it works: if an input (zone) of the communicator is triggered, the G17F sends an event message over mobile internet to the receiver of the monitoring station or to the Protegus 2 app; in addition, it can also send an SMS and make a phone call. The communicator is available with a 2G or a 4G modem. You make the settings with the TrikdisConfig software, over a USB cable or remotely.
| Certification | Data |
|---|---|
| Standard | The G17F meets the requirements of the EN 54-21:2006 standard, and it fulfils the performance requirements specified for a type 1 transmission system in Annex A of EN 54-21. |
| Certificate | 1922-CPR-1974 – Fire detection and fire alarm systems. Alarm transmission and fault warning routing equipment. |
| Certification body | No. 1922 "Dedal" notified product certification body – Nesebar, Mladost str. 50, 8230 Bulgaria |
| Trikdis technical support | support@trikdis.lt, +37067422877 |
1.1 What it is for and how it works
Connection with the fire alarm control panel
- Connected to the outputs of the panel: the status outputs of the panel (alarm, fault etc.) are connected to the inputs of the G17F (section 3.2).
- Over the RS485 bus: to fire alarm control panels with the ESPA 4.4.4 protocol, and to NSC Solution, INIM Smartline and C-TEC Cast ZFP fire alarm control panels (sections 3.3–3.6).
Messages to the monitoring station
- It sends the events to the Trikdis software and hardware receivers, which work with any monitoring software.
- It can also send events to SIA DC-09 receivers.
- If the connection is lost on the primary channel, the messages automatically go to the backup receiver.
- It can also report the events to the monitoring station by SMS – this is extremely useful, because it works even if the IP connection drops in the network of the mobile operator.
- It detects jamming of the mobile network.
- It can report to the monitoring station and send to the Protegus 2 app at the same time; reporting to the monitoring station can be given priority.
- It sends the event messages with Contact ID codes.
Messages to the users
- It calls the selected phone numbers (up to 8 users).
- It sends SMS messages about the events.
- It sends push and special-sound event notifications to the Protegus 2 app.
Remote control of the outputs
- from the Protegus 2 app;
- by calling the phone number of the device;
- by SMS message.
Setup and installation
- Setup with a USB cable or remotely, with the TrikdisConfig software.
- Remote firmware update.
- Two access levels (account types) for the settings: installer and administrator.
Inputs and outputs
- 3 inputs, selectable type: NO, NC, EOL (4.7 kΩ, 10 kΩ).
- 3 dual-purpose I/O terminals that can be set as input (IN) or output (OUT); as input, selectable type: NO, NC, EOL (4.7 kΩ, 10 kΩ).
- RS485 bus for the iO series expansion modules.
- With the iO series expanders, the number of inputs (IN) or outputs (OUT) can be increased to 12.
1.2 Versions
The G17F is available in two cellular versions: with a 2G or a 4G modem. This manual applies to both; the difference is the modem and the mobile network bands.
| Version | Modem | Bands |
|---|---|---|
| G17F-4G | 4G (LTE) | 700 / 800 / 900 / 1800 / 2100 / 2600 MHz |
| G17F-2G | 2G (GSM/GPRS) | 850 / 900 / 1800 / 1900 MHz |
Trikdis G17F 4G GSM / IP communicator
Trikdis G17F 2G GSM / IP communicator
Because 2G networks are being gradually switched off, we recommend the 4G version for new installations.
1.3 Technical specifications
| Parameter | Value |
|---|---|
| 2G (GSM/GPRS) modem bands | 850 / 900 / 1800 / 1900 MHz |
| 4G (LTE) modem bands | 700 / 800 / 900 / 1800 / 2100 / 2600 MHz |
| Supply voltage | 9–32 V DC |
| Current consumption | 100 mA |
| Transmission protocol | TRK, SIA DC-09_2007, SIA DC-09_2012 |
| Encryption key | 6 characters |
| Connection with the monitoring station | TCP/IP or UDP/IP, SMS |
| Event codes | Contact ID |
| Message memory | up to 60 messages |
| Inputs and outputs | 3 inputs: NO, NC, EOL (4.7 kΩ, 10 kΩ); 3 dual-purpose terminals (IN/OUT): as input NO, NC, EOL (4.7 kΩ, 10 kΩ), as output open collector (OC), up to 100 mA |
| Event log | up to 1000 events |
| Setup | remotely with the TrikdisConfig software or locally with a USB Mini-B cable; remotely with SMS messages |
| Length of the RS485 bus | up to 100 m |
| Supported modules | iO expansion module; iO-WL – iO-MOD – iO-WL wireless transceiver; iO-8 expansion module; E485 Ethernet module; W485 (W17u) Wi-Fi module; iO-LORA expansion module; iO8-LORA expansion module; PB-LORA panic button; REL-LORA expansion module; INIM Smartline, NSC Solution and C-TEC Cast ZFP fire alarm control panels; fire alarm control panels with the ESPA 4.4.4 protocol |
| Operating environment | –10 … +50 °C, up to 80 % relative humidity at +20 °C |
| Dimensions | 92 × 62 × 25 mm |
| Weight | 80 g |
The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.
1.4 Parts of the device
The numbers in the figure mark the parts of the device: on the left the front cover, on the right the printed circuit board with the front cover removed.

- 1 SMA connector of the cellular antenna
- 2 indicators (LEDs)
- 3 opening for removing the front cover
- 4 terminal block for connecting the wires
- 5 USB Mini-B connector for programming
- 6 nano-SIM card holder
1.5 The terminals
The names of the terminals can be read on the front cover, above the terminal block (from left to right).
| Terminal | Purpose |
|---|---|
| +DC | supply voltage: positive pole of 9–32 V DC |
| −DC | supply voltage: negative pole of 9–32 V DC |
| 1 IN | input 1, selectable type: NO, NC, EOL (default EOL, 10 kΩ) |
| 2 IN | input 2, selectable type: NO, NC, EOL (default EOL, 10 kΩ) |
| COM | common (negative) terminal |
| 3 I/O | dual-purpose terminal 3 (IN/OUT): as input NO, NC, EOL (default EOL, 10 kΩ), as output open collector (OC), up to 100 mA |
| 4 I/O | dual-purpose terminal 4 (IN/OUT): as input NO, NC, EOL (default EOL, 10 kΩ), as output open collector (OC), up to 100 mA |
| COM | common (negative) terminal |
| 5 I/O | dual-purpose terminal 5 (IN/OUT): as input NO, NC, EOL (default EOL, 10 kΩ), as output open collector (OC), up to 100 mA |
| 6 IN | input 6, selectable type: NO, NC, EOL (default EOL, 10 kΩ) |
| A RS485, B RS485 | RS485 bus: for connecting iO expanders, INIM Smartline, NSC Solution and C-TEC Cast ZFP fire alarm control panels, fire alarm control panels with the ESPA 4.4.4 protocol, and the E485 and W485 modules |
1.6 LED indications
| Indicator | Light | Meaning |
|---|---|---|
| NETWORK | off | not connected to the mobile network |
| green steady and yellow blinking | connected to the mobile network; the number of yellow blinks is the signal strength: on a 2G (GPRS) network 5 blinks, on a 4G network 3 blinks are already enough | |
| DATA | green, steady | message being sent |
| yellow, steady | there are unsent events in the memory | |
| POWER | green blinking | the supply voltage is correct |
| yellow blinking | the supply voltage is not correct | |
| green and yellow blinking | configuration mode | |
| TROUBLE | off | no operating fault |
| 1 blink | no SIM card | |
| 2 blinks | the PIN code of the SIM card is wrong | |
| 3 blinks | cannot connect to the mobile network | |
| 4 blinks | cannot connect to the IP receiver on the primary channel | |
| 5 blinks | cannot connect to the IP receiver on the backup channel | |
| 6 blinks | the internal clock of the G17F is not set | |
| 7 blinks | the supply voltage is not correct | |
| 9 blinks | fault in the connection with the RS485 module |
The correct indication after power-up and the evaluation of the signal strength are described in section 3.13.
1.7 Tools you need for the installation
Before you start the installation, check that you have everything at hand:
- a USB Mini-B cable for the setup;
- a cable with at least 4 wires for connecting the G17F to the fire alarm control panel;
- a 2.5 mm flat screwdriver;
- an external cellular antenna, if the signal is weak at the site;
- an activated nano-SIM card (the PIN request can be switched off);
- the manual of the fire alarm control panel to which you connect the G17F.
The listed accessories must be obtained separately – order them from your dealer. If the signal is weak at the site, use a wired antenna that can be mounted away from the device:
Trikdis ME301M magnetic antenna with 2,5m wire
Trikdis ANT04 GSM stick-on antenna with 2,5m wire
2. Quick setup with the TrikdisConfig software
This chapter describes the settings with which the G17F sends the events to the Protegus 2 app (section 2.1) or to the monitoring station (section 2.2). The other settings of the G17F are in chapter 5.
All Trikdis devices can be programmed using a common software. The software is called TrikdisConfig and can be downloaded from the manufacturer's website.
After downloading, install the program. If a new version is available each time you start TrikdisConfig, download and install the recommended update!
- Remove the front cover of the G17F with a flat screwdriver as shown in the figure.

- Connect the G17F to the computer with a USB Mini-B cable.
- Start TrikdisConfig. The program automatically recognizes the connected device and opens the programming window of the G17F.
- Click the Read [F4] button: the program reads out and shows the current settings of the G17F. If the program asks for the administrator or the installer code, enter the 6-digit code.
Warning
While the device is connected to a computer via USB cable, it is in programming mode: its normal operation stops, it does not monitor, does not report, cannot be controlled, is powered from USB, and restarts once the cable is unplugged. Therefore the device must not be freely accessible: keep it in a closed metal enclosure with tamper protection or with a motion detector covering the enclosure. More in the FAQ
2.1 Setup for the Protegus 2 app
In the Cloud application group of the Users & Reporting page:

- 1 Enable cloud service – switching on the Protegus cloud
- 2 Cloud Access Code – the access code of the cloud (default
123456)
- Tick the Enable cloud service checkbox.
- If you want the users to have to enter the code when they add the system to Protegus 2, change the value of the Cloud Access Code (default
123456).
In the SIM group of the System Options page:

- 3 SIM card PIN – the PIN code of the SIM card
- 4 APN – the mobile internet access point
- Enter the PIN code of the SIM card (SIM card PIN).
- If necessary, change the APN field. You can find the APN on the website of the mobile operator; "internet" is generic and works in the network of most operators. Data of the European operators: APN settings – list of European mobile operators.
- On the Zones page, tick the Prot. checkbox for the zones about whose state changes the users should be notified in Protegus 2 (section 5.6).
- On the PGM page, tick the Prot. checkbox for the PGM outputs about whose state changes the users should be notified in Protegus 2 (section 5.7).
- On the System events page, tick the Prot. checkbox for the internal events of the communicator about whose state changes the users should be notified in Protegus 2 (section 5.8).
At the end of the settings, click the Write [F5] button and unplug the USB cable. Adding the system to the Protegus 2 app: section 4.1.
2.2 Setup for the monitoring station
The monitoring station settings are on two pages. On the System Options page:

- 1 Object ID – object identifier
- 2 SIM card PIN – the PIN code of the SIM card
- 3 APN – the mobile internet access point
- Enter the object identifier (Object ID) you got from the monitoring station: 4 characters, 0–9 and A–F. Do not use the identifiers FFFE and FFFF.
- Enter the PIN code of the SIM card.
- If necessary, change the APN field. You can find the APN on the website of the mobile operator; "internet" is generic and works in the network of most operators.
On the Reporting to CMS page:

- 4 Communication type – the type of connection
- 5 Domain or IP – the address of the receiver
- 6 Port – the port of the receiver
- 7 Protocol – transmission protocol
- 8 Encryption Key – encryption key
- 9 Backup channel – the backup channel
- 10 Backup channel 2 – the phone number of the SMS receiver
- Communication type – select the type of connection (we do not recommend SMS on the primary channel).
- Domain or IP – enter the domain name or IP address of the receiver.
- Port – enter the network port of the receiver.
- Protocol – select the protocol with which the device sends the messages: TRK (for Trikdis receivers), DC-09_2007 or DC-09_2012 (for universal receivers).
- Encryption Key – enter the encryption key of the receiver.
If you report to the monitoring station by SMS, you only need to fill in the Encryption Key and the Phone number fields. The SMS messages are received by the Trikdis RL14 IP/SMS receiver, the RM14 multi-channel receiver and the GM14 SMS receiver. If you select DC-09 as the transmission protocol, also enter the object, line and receiver numbers in the Settings group of the Reporting to CMS page (section 5.3).
- (Recommended) Set up the backup channel (Backup channel).
- (Recommended) Enter the phone number of Backup channel 2.
At the end of the settings, click the Write [F5] button and unplug the USB cable. The other settings of the G17F are described in chapter 5.
3. Installation and wiring
Warining!
It is forbidden to perform wiring on a device under voltage. Before starting the work, disconnect power (including backup batteries).This chapter describes mounting the G17F, wiring the fire alarm control panel (to the outputs of the panel, or over the RS485 bus to the panel with the ESPA 4.4.4 protocol, and to the NSC Solution, INIM Smartline and C-TEC Cast ZFP panels), connecting the inputs and the expansion modules (iO, iO-8, LORA, W485, E485), and finally switching on the communicator. In the drawings, the terminal names of the G17F are the same as the labels on the device (section 1.5).
3.1 Mounting and inserting the SIM card
- Before the installation, make sure that the mobile network signal is strong enough where the G17F will be mounted.
- Remove the front cover and pull off the terminal block.
- Take out the printed circuit board.
- Fix the back of the case to the desired place with screws.
- Put back the printed circuit board and the terminal block.
- Screw on the cellular antenna.
- Insert the nano-SIM card. The SIM card must be registered in a mobile network, and its services must be switched on and working: it must be able to make calls and send and receive SMS, and it must have mobile data. Ask the mobile operator of the SIM card about switching on the services you need.


- Check that the SIM card is activated.
- If you also communicate over an IP channel or with the Protegus 2 app, check that mobile data is switched on.
- If you do not want to enter the PIN code in TrikdisConfig, put the SIM card into a phone and switch off the PIN request.
- For remote setup of the G17F, insert a SIM card with the PIN request switched off, and switch on the power of the communicator. If you have not yet set up the G17F with TrikdisConfig and the Protegus service is not switched on, send it this SMS:
CONNECT 123456 PROTEGUS=ON,APN=INTERNET
- Remote setup of the parameters is described in chapter 6.
- Put back the front cover.
The terminal block can be pulled off: this way the device can be disconnected from power or restarted with one movement, it is easier to handle during wiring, and for USB programming the device can be taken to the computer.
3.2 Wiring to the outputs of the fire alarm control panel
If you want to monitor the state of the fire alarm control panel, connect the appropriate outputs of the panel to the inputs of the G17F. The outputs of the panel (PGM1, PGM2, PGM3) must be set in the panel as status outputs (alarm, fault etc.).

3.3 Fire alarm control panel with the ESPA 4.4.4 protocol
Connect the fire alarm control panel with the ESPA 4.4.4 protocol to the G17F over the RS485 bus, as shown in the drawing below.

Setting up the G17F in TrikdisConfig when it is connected to a fire alarm control panel with the ESPA 4.4.4 protocol:
- On the Modules page, select the ESPA 4.4.4 protocol.
- Select the data transfer rate of the interface (Baudrate).
- The data transfer parameters of the G17F and of the fire alarm control panel must be the same.

- 1 selecting ESPA 4.4.4 protocol
- 2 Baudrate – data transfer rate (9600 in the picture)
- 3 data bits, parity, stop bits and delay (8, None, 1, 40 ms in the picture)
- On the Users & Reporting page, enter the phone numbers of the users who receive messages from the G17F (section 5.4).
- If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox on the SMS & Call reporting tab of the System events page.

- 5 the SMS and Call checkboxes for the ESPA 4.4.4 text event
- If the messages must also reach the receiver of the monitoring station, set up the communication channel on the Reporting to CMS page (sections 2.2 and 5.3). The event messages are sent with the SIA DC-09 protocol.
Try the system: trigger a fire alarm and check that the messages of the G17F arrive at the monitoring station and in Protegus 2.
3.4 NSC Solution fire alarm control panel
Connect the NSC Solution fire alarm control panel to the G17F over the RS485 bus, as shown in the drawing below.

Setting up the G17F in TrikdisConfig when it is connected to an NSC Solution fire alarm control panel:
- On the Modules page, select the NSC Solution module.
- The NSC slave address (the slave address of the communicator) must not be the same as the address of the modules connected to the fire alarm control panel.

- 1 selecting NSC Solution
- 2 NSC slave address – 10 in the picture
- On the Users & Reporting page, enter the phone numbers of the users who receive messages from the G17F (section 5.4).
- The users receive SMS messages and calls about the ticked events (Users & Reporting page, SMS for Panel events tab). In the CID column you can add further Contact ID event codes; next to the new codes you must also enter the text of the SMS. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox.

- 4 the SMS and Call columns of user 1
- If the messages must also reach the receiver of the monitoring station, set up the communication channel on the Reporting to CMS page (sections 2.2 and 5.3).
After setting up the G17F, switch on the power of the fire alarm control panel and wait until the software of the panel has loaded. Then the modules connected to the RS485 bus must be searched for (scanned) on the panel. On the panel, press: PROG. > INSTALLER > (enter the installer code) 00000 OK > (select) SETTINGS > ENTER > (select) SCAN RS485 > ENTER. Wait until the search has finished, then return to the main screen by pressing the CANCEL button twice.
Try the system: trigger a fire alarm and check that the messages of the G17F arrive at the monitoring station and in Protegus 2.
3.5 INIM Smartline fire alarm control panel
Connect the INIM Smartline fire alarm control panel to the G17F over the RS485 bus, as shown in the drawing below.

If you connect the INIM Smartline panel to the G17F over the RS485 bus, the panel must be set to slave mode – you can do this in the SmartLeague program of the panel.

- If repeaters are connected to the INIM Smartline panel, the G17F cannot be connected over the RS485 bus.
- If the G17F is connected to the RS485 bus of the INIM Smartline panel, the iO expansion modules of the communicator are not supported.
Setting up the G17F in TrikdisConfig when it is connected to an INIM Smartline fire alarm control panel:
- On the Modules page, select the Inim Smartline module.

- 1 selecting Inim Smartline
- On the Users & Reporting page, enter the phone numbers of the users who receive messages from the G17F (section 5.4).
- The users receive SMS messages and calls about the ticked events (Users & Reporting page, SMS for Panel events tab – a picture of the tab is in sections 3.4 and 5.4). In the CID column you can add further Contact ID event codes; next to the new codes you must also enter the text of the SMS. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox.
- If the messages must also reach the receiver of the monitoring station, set up the communication channel on the Reporting to CMS page (sections 2.2 and 5.3).
Try the system: trigger a fire alarm and check that the messages of the G17F arrive at the monitoring station and in Protegus 2.
3.6 C-TEC Cast ZFP fire alarm control panel
Connect the C-TEC Cast ZFP fire alarm control panel to the G17F over the ABUS RS485 bus, as shown in the drawing below.

Setting up the G17F in TrikdisConfig when it is connected to a C-TEC Cast ZFP fire alarm control panel:
- On the Modules page, select the C-TEC Cast ZFP fire alarm control panel.

- 1 selecting C-TEC Cast ZFP
- On the Users & Reporting page, enter the phone numbers of the users who receive messages from the G17F (section 5.4).
- The users receive SMS messages and calls about the ticked events (Users & Reporting page, SMS for Panel events tab – a picture of the tab is in sections 3.4 and 5.4). In the CID column you can add further Contact ID event codes; next to the new codes you must also enter the text of the SMS. If you want the user to receive a message (or a call) about the events, tick the SMS (or Call) checkbox.
- If the messages must also reach the receiver of the monitoring station, set up the communication channel on the Reporting to CMS page (sections 2.2 and 5.3).
3.6.1 Setting up the C-TEC panel (ZFPtools)
Install the ZFPtools program on the computer and start it. Switch on the power of the fire alarm control panel and wait until the software of the panel has loaded. Connect the panel to the computer with a USB 2.0 A-B cable.
- Open the Node View tab.

- 1 the Node View tab
- Download the settings of the fire alarm control panel to the computer (Retrieve All Data).

- 2 Retrieve All Data – downloading the settings of the panel
- Enter the code (default
4444). - Click the OK button (the green tick).

- 3 the four code fields
- 4 the OK button (green tick)
- Select the BMS Interface device (Device Palette).
- Click a free icon position.

- 5 BMS Interface in the Device Palette list
- 6 free icon position (no. 16 in the picture)
- Click the Edit Devices button.

- 7 Edit Devices
- On the Device tab, enter the name of the system.

- 8 Name – the name of the system
- On the Properties tab, enter the name of the system.
- Select the ABUS RS485 bus to which the G17F is connected.
- Set up the messages.
- Write the settings into the fire alarm control panel (Send All Data).

- 9 Name – the name of the system (FIRECOM)
- 10 Connection – ABUS RS485
- 11 the messages: Zone Disablements – Reports Zone; Input Group Disablements, Output Group Disablements and Group Actions – Reports Group
- 12 Send All Data – writing the settings into the panel
- Enter the code (default
4444) – in the same Panel Log In window as in step 3. - Click the OK button.
The fire alarm control panel is programmed. Unplug the USB 2.0 A-B cable from the panel.
Try the system: trigger a fire alarm and check that the messages of the G17F arrive at the monitoring station and in Protegus 2.
3.7 Wiring the inputs
The communicator has six input terminals (1 IN – 6 IN; three of them are dual-purpose, IN/OUT), to which NO, NC and EOL (4.7 kΩ, 10 kΩ) type circuits can be connected. By default the inputs monitor an EOL type circuit; you can set another type on the Zones page of TrikdisConfig (section 5.6).
| Wiring | Normal (restore) | Alarm |
|---|---|---|
| NO – normally open contact | open | short circuit |
| NC – normally closed contact | short circuit | open |
| NO + EOL – open contact with a 10 kΩ resistor in parallel | 10 kΩ | short circuit or open |
| NC + EOL – closed contact with a 10 kΩ resistor in series | 10 kΩ | short circuit or open |
Drawings of the four wiring modes; the contact goes between the COM and the INx terminal, 10k is the 10 kΩ end-of-line resistor.




3.8 iO series expansion modules
If the communicator needs more inputs (IN) or outputs (OUT), connect a wired or wireless Trikdis iO series input and output expander to it.

- red wire ("Red wire")
- blue wire ("Blue wire")
- black wire ("Black wire")
- white wire ("White wire")
- W wireless connection ("Wireless connection"), up to 300 m ("up to 300 m")
The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.
3.9 iO-8 expansion module
If the communicator needs more inputs (IN) or outputs (OUT), connect an iO-8 wired expander to it. Detailed description of the expander: iO8 input and output expander – installation manual.
Trikdis iO8 wired expander module

3.10 LORA series expansion modules
The LORA modules connect to the G17F by radio: the RF-LORA transceiver goes on the RS485 bus, and it keeps the connection at up to 5000 m with the iO-LORA, iO8-LORA and REL-LORA expanders and the PB-LORA panic button. You add the modules on the Modules page of TrikdisConfig (section 5.5).

- W wireless connection ("Wireless connection"), up to 5000 m ("up to 5000 m")
The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.
Trikdis RF-LORA wireless expander module
Trikdis IO-LORA wireless expander module
Trikdis IO8-LORA wireless expander module
Trikdis PB-LORA wireless panic button
3.11 W485 Wi-Fi module
The W485 module sends the messages of the G17F over Wi-Fi, through the internet router, to the monitoring station and to the Protegus 2 app. As long as there is a Wi-Fi connection, the G17F sends the event messages through the W485; if the Wi-Fi connection is lost, it sends them over the mobile network (GPRS), and when the Wi-Fi connection is restored, it returns to the W485. The function works from firmware 1.08 of the G17F. With the W485, the G17F can also be used without a SIM card. Setting up the W485 for the G17F: section 5.5.
Trikdis W485 Wifi module (RS485)

- 1 power supply ("Power supply"), 12 V DC, 0.5 A
The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.
3.12 E485 Ethernet module
The E485 module sends the messages of the G17F over a wired internet connection to the monitoring station and to the Protegus 2 app. With the E485, the messages go over the wired internet, the G17F does not use mobile internet. If the wired internet connection is lost, the G17F sends the messages over mobile internet, and when the wired connection is restored, again through the E485. The function works from firmware 1.08 of the G17F. With the E485, the G17F can also be used without a SIM card. Setting up the E485 for the G17F: section 5.5.
Trikdis E485 Ethernet module (RS485)

- 1 power supply ("Power supply"), 12 V DC, 0.5 A
The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.
3.13 Switching on the communicator
To switch on the communicator, you must first provide power to the fire alarm control panel (in the drawings the G17F gets its power from the 24 V output of the panel). If the communicator works correctly, these indicators are lit:
- the POWER LED blinks green (the supply voltage is correct);
- the NETWORK LED is lit green, and blinks yellow when the communicator has connected to the network.
- Sufficient mobile network signal strength: 5 on a 2G network (five yellow blinks of the NETWORK LED), 3 on a 4G network (three yellow blinks).
- If you count fewer than 3 yellow blinks on the NETWORK LED, the signal strength is not sufficient: choose another installation place, or use a more sensitive antenna (section 1.7).
- If the indication is different from this, you will find the explanation in section 1.6.
- If none of the indicators of the G17F is lit, check the power supply and the wiring.
4. Remote control
The G17F can be controlled from the Protegus 2 app, by SMS command and by phone call (with the phone's keypad during the call). In the app the users also see the state of the system and receive notifications about the system events; by SMS the administrator can also change part of the settings.
4.1 Adding the G17F to Protegus 2
In Protegus 2 the users see the state of the system and receive notifications about the system events. The app is available for phones and in the browser (the download links are below, at creating the system).
Before you add the system
You can add the G17F to Protegus 2 if:
- there is an activated SIM card in it, and you have entered or switched off the PIN code;
- the Protegus service is switched on (Users & Reporting → Enable cloud service, section 5.4; by SMS:
CONNECT 123456 PROTEGUS=ON, section 4.2); - its power is switched on (the POWER LED blinks green);
- it is connected to the network (the NETWORK LED is lit green and blinks yellow).
The DATA LED is the simplest internet check. The DATA LED is lit when there is a message waiting to be sent in the device's memory. A green NETWORK LED only tells you that the network connection has been established – for a mobile network device, that it has registered on the operator's network; for an Ethernet device, that the connection up to the router is alive – but not that the device can also reach the internet. If the NETWORK LED is green but the DATA LED stays lit continuously even after an event or test report, the internet connection is not working: the message cannot be sent. On a mobile network the most common culprit is the APN or the data service of the SIM card; on Ethernet, the router, the firewall or the DNS. When the DATA LED goes out, the message has been sent and the data connection is fine.
Creating the system in the Protegus 2 application
- Download the Protegus 2 application to your phone or open it in a browser
- Register an account if you haven't already.
- Log into your account.
- On the main page, click the "+" button to create a system
- Enter the unique identifier of the TRIKDIS device (you can also scan the barcode or QR code with your phone's camera), which you can find
- On the sticker of the device
- On the device's cardboard box
- In the bottom left corner of TrikdisConfig (selectable and copyable format)
- Enter the system name and select a time zone
- Your system is created, you can still name the partitions and zones at the next step, but you can do this later anytime.
- In the last step, your system's home screen will appear. Wait until the yellow stripe disappears and your system is ready.
For the G17F, pay attention to the following when adding it:
- After entering the unique identifier (Unique ID), click the Next button. You find the identifier on the sticker on the device and on the box; with a USB connection you also see it in the TrikdisConfig status bar (IMEI/Unique ID, section 5.1).
- If the installer has changed the default
123456value of the Cloud Access Code, the app asks for the code when you add the system (section 2.1).
4.2 Setup and control by SMS message
1. Change the administrator password. For security, replace the default administrator SMS password. Send an SMS in this form:
PSW 123456 xxxxxx
| Part | Meaning |
|---|---|
123456 |
the default administrator password |
xxxxxx |
the new, 6-character administrator password |
2. Allow control for other users. By SMS and phone call, the system can only be controlled from the phone numbers on the user list. From the administrator's phone, send an SMS with the phone numbers and names of the other persons, so that they can also control the system:
SETN xxxxxx PHONEx=+PHONENR#NAME
| Part | Meaning |
|---|---|
xxxxxx |
the 6-character administrator password |
x |
the number of the user on the list (if you enter 1, you hand over your administrator rights to the other user) |
PHONENR |
the phone number of the user |
NAME |
the name of the user |
List of SMS commands
| Command | Data | Description |
|---|---|---|
INFO |
Request for data about the communicator: the reply contains the type, IMEI number, serial number and firmware version of the communicator. Example: INFO 123456 |
|
RESET |
Restarting the device. Example: RESET 123456 |
|
OUTPUTx |
ON |
Switching on an output; "x" is the number of the output. Example: OUTPUT1 123456 ON |
OUTPUTx |
OFF |
Switching off an output; "x" is the number of the output. Example: OUTPUT1 123456 OFF |
OUTPUTx |
PULSE=ttt |
Switching on an output for a few seconds: "x" is the number of the OUT output, "ttt" is a three-digit number, the pulse time in seconds. Example: OUTPUT1 123456 PULSE=002 |
PSW |
new password | Changing the password. Example: PSW 123456 654123 |
TIME |
YYYY/MM/DD,12:00:00 |
Setting the date and time. Example: TIME 123456 2025/05/09,10:23:00 |
TXTA |
object name | Entering the name of the object. Example: TXTA 123456 House |
TXTE |
Z1= … Z12= |
Entering the SMS text of the zone alarm; Z1…Z12 is the number of the input zone. Example: TXTE 123456 Z1=ALARM in Zone1 |
TXTR |
Z1= … Z12= |
Entering the SMS text of the zone restore; Z1…Z12 is the number of the input zone. Example: TXTR 123456 Z1=Restore Zone1 |
RDR |
PhoneNR#SMStext |
Forwarding an SMS to the given number; the phone number must start with "+" and the international country code. Example: RDR 123456 +37061234567#forwarded text |
ASKI |
SMS query about the state of the inputs (IN). Example: ASKI 123456 |
|
ASKO |
SMS query about the state of the outputs (OUT). Example: ASKO 123456 |
|
SETN |
PhoneX=PhoneNR#Name |
Adding a phone number and user name to user "x" ("x" is the line of the phone number on the list). The phone number must start with "+" and the international country code; the phone number and the user name are separated by a # sign. Example: SETN 123456 PHONE5=+37061234567#JOHN |
SETN |
PhoneX=DEL |
Deleting the phone number and name of the user from the system. Example: SETN 123456 PHONE5=DEL |
UUSD |
*Uusd code# |
Sending a USSD code to the operator (the name of the command really is UUSD). Example: UUSD 123456 *245# |
CONNECT |
Protegus=ON |
Connecting to the Protegus cloud service. Example: CONNECT 123456 PROTEGUS=ON |
CONNECT |
Protegus=OFF |
Disconnecting from the Protegus cloud service. Example: CONNECT 123456 PROTEGUS=OFF |
CONNECT |
Code=123456 |
The code of the Protegus cloud service. Example: CONNECT 123456 CODE=123456 |
CONNECT |
IP=0.0.0.0:8000 |
The TCP IP address and port of the connection channel of the main server. Example: CONNECT 123456 IP=0.0.0.0:8000 |
CONNECT |
IP=0 |
Switching off the main channel. Example: CONNECT 123456 IP=0 |
CONNECT |
ENC=123456 |
The TRK encryption key. Example: CONNECT 123456 ENC=123456 |
CONNECT |
APN=Internet |
The name of the APN. Example: CONNECT 123456 APN=INTERNET |
CONNECT |
USER=user |
The user name of the APN. Example: CONNECT 123456 USER=User |
CONNECT |
PSW=password |
The password of the APN. Example: CONNECT 123456 PSW=Password |
4.3 Controlling the PGM outputs by phone call
If no user has been added to the system yet, the first person who calls the G17F becomes the administrator of the system, and only they can control the G17F by call and SMS commands. If you want to allow control by call for further users too, add them in TrikdisConfig (section 5.4), or give them the right by SMS command (section 4.2).
If you want to control a PGM output remotely:
- The user must have the right to control the outputs (OUT) (section 5.4), and the Remote control type must be assigned to the output (OUT) in TrikdisConfig (PGM page, Output definition, section 5.7).
- Call the number of the SIM card of the G17F. The G17F answers the call, and you can key in commands with the phone's keypad according to the table.
| Keys | Function | Description |
|---|---|---|
[output]*[state]# |
controlling the selected output (OUT) | It switches the given PGM output. State: 0 – output switched off; 1 – output switched on; 2 – switched off for the pulse time; 3 – switched on for the pulse time (the pulse time can be set in the PGM table of TrikdisConfig, section 5.7). The # marks the end of the command. Examples: switching on output 1: 1*1#; switching off output 1: 1*0#; switching on output 2 for the pulse time set in the PGM table: 2*3# |
# |
restarting the command | If you made a mistake in the command, press the # key of the phone and key in the command again. |
5. The pages of TrikdisConfig
This chapter describes the pages of the TrikdisConfig programming window, in the order in which they follow in the left-hand menu. Connecting the G17F with a USB cable: chapter 2; remotely: chapter 6.
5.1 The status bar
After connecting the device and reading it (Read [F4]), the most important device data are shown at the bottom of the window:
| Label | Meaning |
|---|---|
| IMEI / Unique ID, on an Ethernet device MAC / Unique ID | The device's unique identifier: the IMEI on a device with a SIM card, the MAC address on an Ethernet device. The same is printed on the box and on the back of the device. |
| Status | The current operating status. |
| Device | The device type (model designation). Check that the type of your own device is shown here. |
| SN | Serial number. |
| BL | The bootloader version. |
| FW | The firmware version. |
| HW | The hardware version. |
| State | The connection mode: USB or remote. |
| Administrator / Installer | The access level of the person programming (after the password has been entered). |
After making the settings, you write them to the device with the Write [F5] button; with the Open [F8] and Save [F9] buttons you can save the complete set of settings to a file and load it into another device. Save [F9] saves the settings to a settings file, and Open [F8] opens the saved file; you can later load the saved settings into other devices as well, so you can quickly set up several devices with identical settings.

When you click the Read [F4] button, the program reads out and shows the current settings stored on the G17F. Set the necessary parameters according to the following page descriptions.
5.2 "System Options" page
The general settings of the device on two tabs: System general and Access.
System general tab

General group
- Object ID – if the events go to the monitoring station, enter the object identifier you got from the monitoring station (4-character hexadecimal number, 0–9, A–F). Do not use the identifiers FFFE and FFFF.
- Object name – the name of the object; this name appears in the SMS messages sent to the users.
- Test period – when ticked, the G17F sends a "Test" message at the set interval.
- Time set – the source of time synchronization. IP server: the time follows the time of the IP receiver; Cellular modem (GSM modem in the picture): the time of the mobile operator's server.
- Clear Events after reset – when ticked, all unsent event messages are deleted at restart (reset).
- Text language – the language of the SMS messages: the device uses the special characters of the selected language in the SMS messages.
- Suspend event reporting when … same events per … s – suspending event reporting if the given number of identical events repeats within the given number of seconds.
- Restore event reporting after … min – after this time the suspension of event reporting ends (0–999 minutes).
- Low power voltage – enter the supply voltage (12 V or 24 V) the device operates from; the messages about low supply voltage follow this.
SIM group
- SIM card PIN – the PIN code of the SIM card.
- APN – the name of the mobile internet access point of the mobile operator. You must enter it if the event messages go over a mobile data connection to the Protegus 2 app or to the monitoring station. Data of the European operators: APN settings – list of European mobile operators.
- Login, Password – the user name and password of the APN, if the mobile operator requires them.
Time zone group
- Time zone – the time zone of the country (for example Central European Time: +1).
- Daylight saving time – when ticked, the internal clock of the device automatically switches between summer and winter time.
Access tab
On the Access tab you set the access codes and the permissions of the installer.

Access codes group
- Administrator Code – full access to the settings (default
123456). - SMS password – password for remote control and programming by SMS (default
123456). - Installer Code – limited access for changing the settings (default
654321).
Installer permissions group – here the administrator sets which parameters the installer may change.
For security, change the default codes. You can also change the SMS password by SMS (PSW, section 4.2).
5.3 "Reporting to CMS" page
The G17F sends the messages to the monitoring station over mobile internet (IP) or by SMS. A backup channel can be assigned to the primary channel: the device uses it if the connection is lost on the primary channel.

The messages sent to the monitoring station are encoded and password-protected. To receive the messages and forward them to the monitoring software, a Trikdis receiver is needed:
- for IP messages: the IPcom receiver software (Windows or Linux), the RL14 IP/SMS hardware receiver or the RM14 multi-channel receiver;
- for SMS messages: the RL14 IP/SMS hardware receiver, the RM14 multi-channel receiver or the GM14 SMS receiver.
Trikdis IPcom v5 Windows software receiver
Trikdis IPcom v5 Linux software receiver
The SMS connection is extremely useful as a backup channel, because it works even if the internet connection drops in the network of the mobile operator. We do not recommend SMS as the primary channel.
Primary channel group
- Communication type – the mode of connection with the receiver of the monitoring station.
- Domain or IP – the domain name or IP address of the receiver.
- Port – the network port of the receiver.
- Protocol – the Trikdis IP receivers receive messages sent with the TRK protocol; for IP receivers able to receive SIA DC-09 messages, select the DC-09_2007 or the DC-09_2012 protocol.
- Phone number – (only for SMS) the phone number of the Trikdis SMS receiver, starting with the country code (for example CCxxxxxxxxx, where CC is the country code).
- Encryption Key – 6-digit encryption key; it must match the encryption key of the receiver.
Backup channel group – switch it on so that the G17F sends the messages on the backup channel when the connection is lost. Its settings are the same as those of the primary channel.
Settings group
- Return to Primary after – after this time the G17F tries to return to the primary channel.
- IP Ping period – the sending interval of the internal PING signals that check the connection. The PING signals only go over the IP channel; the receiver does not forward them to the monitoring software, so they do not load it. The software is only notified if the receiver gets no PING from the device for the set time.
- SMS Ping period – the interval of the PING signal sent on the SMS channel, in minutes. To use the channel, tick the checkbox and enter the interval.
- Backup reporting after – after how many unsuccessful sending attempts the G17F sends on the backup channel (Backup channel).
- DNS1, DNS2 – the DNS servers that translate the domain name into an IP address. They are needed if you entered a domain name (and not an IP address) in the Domain or IP field of the channel. By default, the DNS servers of Google.
The PING interval
By default, the receiver sends a "Connection lost" message to the monitoring software if it gets no PING within three times the PING sending interval of the device: with a 3-minute IP Ping period, for example, after 9 minutes. The PING messages also keep the connection between the device and the receiver active – the active connection is needed for remote setup and control. We recommend setting the PING interval to at most 5 minutes.
The fields below are only visible if you selected the DC-09_2007 or DC-09_2012 protocol in the Protocol field of the channel:
- Object ID in SIA DC-09 – the object number; with the DC-09 protocol this number goes into the messages. Enter the 3–16-character hexadecimal number you got from the monitoring station.
- SIA DC-09 receiver No. – the number of the receiver.
- SIA DC-09 line No. – the number of the line in the receiver.
Backup channel 2 group
- Phone number – (only for SMS) the phone number of the Trikdis SMS receiver, starting with the country code (for example CCxxxxxxxxx, where CC is the country code).
5.4 "Users & Reporting" page
The settings of the users, the Protegus cloud and the SMS replies, on three tabs: Users, SMS answer texts and SMS for Panel events.
Users tab
On the Users tab you enter the users who receive SMS messages and calls, and here you switch on the Protegus cloud.

Users & Reporting to User group
- ID – the number of the user on the list.
- Name – the name of the user; this name appears in the event SMS messages.
- Tel number – the phone number of the user, to which the SMS messages go; enter it in international format (+CC…, where CC is the country code).
- PGM – when ticked, the user can control the outputs remotely (this column is not visible in the picture above).
- ACK – when ticked, the G17F sends a reply SMS to the user after every SMS command received (the text of the replies: SMS answer texts tab).
- FWD – when ticked, the G17F forwards to the user the SMS messages coming from numbers outside the system (for example the balance notification of the SIM card or advertising messages).
Cloud application group
- Enable cloud service – switching on the Protegus service: this way the G17F exchanges data with the Protegus 2 app, and it can also be set up remotely with TrikdisConfig (chapter 6).
- Parallel reporting – parallel sending: the messages go on the primary channel and to Protegus 2 at the same time.
- Cloud Access Code – 6-digit code for logging in to Protegus 2 (default
123456).
SMS answer texts tab
In the SMS text column you can edit the text of the replies sent to the SMS commands.

SMS for Panel events tab
This tab only appears if you have entered at least one user phone number on the Users tab. Here you set whether the users receive an SMS and/or a call about the events of the fire alarm control panel.

- Zn – the number of the event on the list.
- CID – the Contact ID code of the event.
- SMS text – the SMS text of the event.
- User SMS/Call – for each event you can select whether the user receives an SMS and/or a call.
The modem places the call over 2G or VoLTE. Where the operator has switched off 2G and has not approved the modem for VoLTE, the SMS arrives but the phone does not ring. This is not a configuration error. In such places, use SMS and the Protegus 2 app.
5.5 "Modules" page
The list of the modules and fire alarm control panels connected to the RS485 bus, and the settings of the W485 and E485 modules.
RS485 modules tab
In the list you enter one module or fire alarm control panel per line (up to 8).

- ID – the number of the module on the list.
- Module – the module or panel used: iO, iO-WL, iO-8, INIM Smartline, E485, W485, iO-LORA, iO8-LORA, PB-LORA, REL-LORA, NSC Solution, C-TEC Cast ZFP, ESPA 4.4.4.
- Serial No. – mandatory, 6-digit number; you find it on the case and on the packaging of the module.
- Name – the name of the module (any name).
- Firmware version – the firmware version of the module; it appears when the G17F finds the connected module.
W485 settings tab
The settings of the W485 (W17u) Wi-Fi module (wiring: section 3.11).

Communicator network settings group
- DHCP mode – the mode of network registration of the Wi-Fi module (manual or automatic). When ticked (automatic mode), the module automatically recognizes the network settings (subnet mask, gateway) and gets an IP address.
- Static IP – static IP address in manual mode.
- Subnet mask – subnet mask in manual mode.
- Default gateway – default gateway in manual mode.
- Wifi SSID name – the name of the Wi-Fi network to which the W485 (W17u) connects.
- Wifi SSID password – the password of the Wi-Fi network.
SIM parameters group
- Disable indication of the absence of a SIM card – when ticked, the G17F does not indicate if there is no SIM card in it.
- Use dial and SMS when working over internet module – when ticked, the G17F can also be controlled by call and SMS. If it is not ticked and there is a Wi-Fi network, calls and SMS are not used; if it is not ticked and there is no Wi-Fi network, the G17F handles the calls and SMS messages, and sends an SMS to the user.
- Disable the use of SIM card mobile data – when ticked, the G17F does not use the mobile data connection of the SIM card: the data only go through the W485 module. If the Wi-Fi network is lost, the G17F stores the data in its memory, and after the Wi-Fi returns it sends them through the W485 module.
E485 settings tab
The settings of the E485 Ethernet module (wiring: section 3.12).

Communicator network settings group
- DHCP mode – the mode of network registration of the Ethernet module (manual or automatic).
- Static IP – static IP address in manual mode.
- Subnet mask – subnet mask in manual mode.
- Default gateway – default gateway in manual mode.
SIM parameters group
- Disable indication of the absence of a SIM card – when ticked, the G17F does not indicate if there is no SIM card in it.
- Use dial and SMS when working over internet module – when ticked, the G17F can also be controlled by call and SMS. If it is not ticked and there is internet, SMS and calls are not used; if it is not ticked and there is no internet, the G17F handles the calls and SMS messages, and sends an SMS to the user.
- Disable the use of SIM card mobile data – when ticked, the G17F does not use the mobile data connection of the SIM card: the data only go through the E485 module. If the internet is lost, the G17F stores the data in its memory, and after the internet returns it sends them through the E485 module.
5.6 "Zones" page
The settings of the zones (inputs) on two tabs: Zones settings and SMS & Call reporting.
Zones settings tab
In the table you set up one zone per line.

- Zone No – the number of the zone on the list.
- Name – the name of the zone; this name appears in the SMS messages.
- Input – which input (IN) of the G17F or of the expansion module belongs to the zone.
- Definition – every zone has the 24 hours definition: if the zone is triggered, the event message is sent immediately.
- Type – the type of the circuit connected to the input: NC – normally closed contact; NO – normally open contact; EOL – circuit terminated with an end-of-line resistor (4.7 kΩ or 10 kΩ) (section 3.7).
- CMS – when ticked, the events of the zone go to the monitoring station.
- Prot. – when ticked, notifications about the events of the zone go to the Protegus 2 app.
- Delay – the reaction time of the input (IN) in milliseconds.
- CID Code – the Contact ID code of the event.
- SIA E – the SIA event code.
- SIA R – the SIA restore code.
- LOOP – the number of the loop; it appears in the SMS message.
SMS & Call reporting tab
This tab only appears if you have entered at least one user phone number on the Users & Reporting page.

- Zn – the number of the zone with the keyword of the event: Event or Restore.
- SMS text – the description of the zone event; this goes into the event SMS sent to the users.
- User SMS/Call – for each zone event you can select whether the user receives an SMS and/or a call.
5.7 "PGM" page
The settings of the PGM outputs on two tabs: Outputs and SMS & Call reporting.
Outputs tab
In the table you set up one PGM output per line.

- PGM No – the number of the PGM output on the list.
- PGM output – the output (OUT) assigned to the PGM: of the G17F or of an external device.
- Output definition – the operating mode of the output (OUT).
- Pulse time, s – the duration for which the output (OUT) is switched on, 0–9999 seconds.
- CMS – when ticked, the selected events go to the monitoring station.
- Prot. – when ticked, notifications about the events of the output go to the Protegus 2 app.
- SIA E – the SIA event code.
- SIA R – the SIA restore code.
SMS & Call reporting tab
This tab only appears if you have entered at least one user phone number on the Users & Reporting page.

- PGM – the number of the output (OUT) and the type of the event: Event – switching on the output; Restore – switching off the output.
- SMS text – the name of the switch-on or switch-off event of the output; this goes into the event SMS.
- User SMS/Call – you can select which users receive an SMS and/or a call when the output (OUT) is switched on and off.
5.8 "System events" page
The settings of the communicator's own (system) events on two tabs: Events and SMS & Call reporting.
Events tab
In the table you set up one system event per line.

- ID – the number of the event on the list.
- Event name – the name of the event.
- Enable – switching on the monitoring of the event.
- CMS – the selected events go to the monitoring station.
- Prot. – notifications about the selected events go to the Protegus 2 app.
- CID Code – the Contact ID code of the event.
- SIA E – the SIA event code.
- SIA R – the SIA restore code.
- LOOP – the number of the loop; it appears in the SMS message.
- SMS event text – the SMS text of the event.
- SMS restore text – the SMS text of the restore.
SMS & Call reporting tab
This tab only appears if you have entered at least one user phone number on the Users & Reporting page.

- ID – the number and keyword of the event (Event, Restore).
- Event SMS text – the text of the event that goes into the SMS message.
- User SMS/Call – for each event you can select whether the user receives an SMS and/or a call.
5.9 "Events Log" page
Here you can read out and delete the event log of the device.

- Read Log – the button reads out the event log from the memory of the device.
- Clear Log – the button deletes the log entries from the memory of the device.
- The table shows the number (Event No.), time (Time), CID code and description (Event definition) of the event. The log shows up to 1000 events stored in the memory of the G17F.
5.10 Restoring the factory settings
To restore the factory settings of the G17F, click the Restore button of TrikdisConfig (in the lower left part of the programming window, in the Default settings line).

If you may need the current settings later, save them to a file with the Save [F9] button before restoring (section 5.1).
6. Remote programming
You can also read out and change the settings of the G17F remotely through the Protegus cloud with TrikdisConfig – you do not need to go to the site.
Conditions for remote programming
Remote setup only works if, in the G17F:
- there is an activated SIM card, and you have entered or switched off the PIN code;
- the Protegus service is switched on (Users & Reporting → Enable cloud service, section 5.4);
- its power is switched on (the POWER LED blinks green);
- it is connected to the network (the NETWORK LED is lit green and blinks yellow).
If the NETWORK or the DATA LED is lit yellow continuously, the device cannot connect to the mobile network and/or to Protegus 2.
- Start TrikdisConfig on the computer.
- In the Remote access section, enter the unique identifier of the G17F (Unique ID) in the Unique ID field. You find this number on the back of the device and on its packaging.

- (Optional) In the System Name field, enter a name for the device (for example the name of the object).
- Click the Configure button.
- In the window that opens, click the Read [F4] button. If the program asks for it, enter the administrator or the installer code.
- At the end of the settings, click the Write [F5] button. When you have finished with TrikdisConfig, click the Disconnect button.
7. Checking the operation
At the end of the setup and installation, test the whole system:
- To check an input, activate (trigger) the input. Check whether the event has arrived at the monitoring station and/or in the Protegus 2 app.
- To check the outputs, switch them on remotely and check their operation. Make sure that the events have arrived at the monitoring station and/or in the Protegus 2 app.
- Carry out a fire alarm test, and check that the monitoring station receives the events correctly.
The DATA LED is the simplest internet check. The DATA LED is lit when there is a message waiting to be sent in the device's memory. A green NETWORK LED only tells you that the network connection has been established – for a mobile network device, that it has registered on the operator's network; for an Ethernet device, that the connection up to the router is alive – but not that the device can also reach the internet. If the NETWORK LED is green but the DATA LED stays lit continuously even after an event or test report, the internet connection is not working: the message cannot be sent. On a mobile network the most common culprit is the APN or the data service of the SIM card; on Ethernet, the router, the firewall or the DNS. When the DATA LED goes out, the message has been sent and the data connection is fine.
You can also query the data of the communicator and the state of the inputs and outputs by SMS: INFO 123456, ASKI 123456, ASKO 123456 (replace 123456 with your own SMS password; section 4.2).
8. Firmware update
If you connect the G17F to TrikdisConfig and newer firmware is available, the program offers the update by itself – for this the computer must be connected to the internet. Antivirus software, a firewall or strict internet access settings can block the automatic update.
You can update the firmware yourself – to a newer version and, if necessary, to an older one as well. All device settings remain unchanged after the update.
- Start the TrikdisConfig software and connect the device with a USB cable, or open its programming remotely.
- If newer firmware is available, the software offers to download it – accept it.
- Select the Firmware page and click the Open firmware button. Select the firmware file.
- Press the Update [F12] button, wait for the update to finish, then click OK in the pop-up window. Do not unplug the cable or interrupt the connection in the meantime.
The firmware files are in the TrikdisConfig installation folder, inside the Firmwares subfolder, in the folder named after the device. If there is no such folder, either there is no update for it or the TrikdisConfig software itself needs to be updated. The latest files can also be downloaded as a registered user from the device's page on the manufacturer's website.
![TrikdisConfig – G17F, **Firmware** page: the **Open firmware file** field, the **Open firmware** button, the **Update [F12]** button and the progress indicator.](/image/catalog/content/manuals/g17f/tc_firmware.png)
To use the W485 and E485 modules, G17F firmware 1.08 or newer is needed (sections 3.11 and 3.12); you see the current version in the FW field of the status bar (section 5.1).
9. Troubleshooting and frequently asked questions
If the communicator does not do what you expect, first look at the indicators (section 1.6), then at the points below.
The TROUBLE LED is blinking – what does the number of blinks mean?
The number of blinks is the cause of the fault: 1 – no SIM card; 2 – the PIN code of the SIM card is wrong (System Options → SIM card PIN, section 5.2); 3 – cannot connect to the mobile network; 4 – cannot connect to the IP receiver on the primary channel (Reporting to CMS, section 5.3); 5 – cannot connect to the IP receiver on the backup channel; 6 – the internal clock is not set (Time set, section 5.2; by SMS: TIME, section 4.2); 7 – the supply voltage is not correct (9–32 V DC; Low power voltage, section 5.2); 9 – fault in the connection with the RS485 module (wiring: sections 3.3–3.12; Modules, section 5.5).
How many yellow blinks are needed on the NETWORK LED?
The number of yellow blinks shows the signal strength: on a 2G (GPRS) network 5, on a 4G network 3 blinks are already enough. If you count fewer than 3 yellow blinks, the signal strength is not sufficient: choose another place for the communicator, or use a more sensitive antenna that can be mounted away from the device (section 1.7). If the indicators are not lit at all, check the power and the wiring (section 3.13).
Protegus 2 does not find the communicator
- Check the conditions for adding it: activated SIM card, PIN code entered or switched off, Protegus service switched on (Users & Reporting → Enable cloud service, section 5.4), POWER LED blinking green, NETWORK LED lit green and blinking yellow (section 4.1).
- If the NETWORK or the DATA LED is lit yellow continuously, the device cannot connect to the mobile network and/or to Protegus 2 (chapter 6). Check the APN setting (section 5.2).
- If the Cloud Access Code is not the default
123456, enter the correct code when adding the system (section 2.1).
I cannot control the outputs by call or SMS
- By SMS and call, control is only possible from the phone numbers on the user list (section 4.2). If no user has been added yet, the first caller becomes the administrator (section 4.3).
- The user must have the right to control the outputs (PGM checkbox, section 5.4), and the Remote Control definition must be assigned to the output (Output definition, section 5.7).
- With a W485 or E485 module, check the Use dial and SMS when working over internet module checkbox (section 5.5): if it is not ticked and there is an internet connection, calls and SMS are not used.
I get no reply to my SMS commands
For the reply SMS, the ACK checkbox must be ticked for the user (Users & Reporting, section 5.4). You can edit the text of the replies on the SMS answer texts tab.
Where do the operator's SMS messages (balance, advertising) go?
If the FWD checkbox is ticked for the user, the G17F forwards to them the SMS messages coming from numbers outside the system (for example the balance notification of the SIM card) (section 5.4).
INIM Smartline: what should I pay attention to?
The panel must be set to slave mode in the SmartLeague program. If repeaters are connected to the panel, the G17F cannot be connected over the RS485 bus; and if the G17F is connected to the RS485 bus of the panel, the iO expansion modules of the communicator are not supported (section 3.5).
NSC Solution: the panel does not see the communicator
After setting up the G17F, the modules connected to the RS485 bus must be searched for (scanned) on the panel (SCAN RS485, section 3.4). The NSC slave address must not be the same as the address of the other modules connected to the panel.
What interval should I set for the PING?
We recommend a PING interval of at most 5 minutes. By default, the receiver reports the loss of connection to the monitoring software after three times the PING interval; the active connection is also needed for remote setup and control (section 5.3).
Can the G17F be used without a SIM card?
Yes, with a W485 Wi-Fi module or an E485 Ethernet module (with G17F firmware 1.08 or newer): in this case the messages go through the module (sections 3.11 and 3.12). If the Wi-Fi or the wired internet is lost, the G17F would send over the mobile network – this backup needs a SIM card. The settings of the module, for example indicating the absence of the SIM card and disabling mobile data: section 5.5.
10. Safety instructions
Attention!
Electricity can be dangerous and may cause personal injury or DEATH, as well as other financial loss or damage if not used or installed properly.
Installation involves working with electrical equipment, and it should be executed in accordance with current regulations!
Warranty validation requires the device to be installed by a qualified person following the installation regulations for electrical equipment and adhering to the current regulations for the safe operation of electrical equipment.
- The communicator may only be installed and maintained by qualified persons.
- Before installation, read this manual carefully to avoid mistakes that can lead to malfunction or even damage to the equipment.
- Disconnect the power before making any electrical connection.
- Changes, modifications or repairs not authorized by the manufacturer void the warranty.
- Follow local waste disposal regulations: do not throw the device and its parts in household waste – hand in the discarded device as electronic waste.
See also
- iO8 input and output expander – installation manual – the iO-8 expansion module for the G17F.
- APN settings – list of European mobile operators – if the mobile data connection is not established.
- Protegus Android / iPhone and web app – about the app.
- Protegus 2 Business Account – managing several systems as an installer.
- Documentation in English: docs.trikdis.com – LTE communicator for fire alarm control panels G17F – the manuals on docs.trikdis.com are in English.