RF-LORA wireless transceiver – installation and setup manual
Installation and setup manual for the Trikdis RF-LORA wireless transceiver: connection to the FLEXi SP3 alarm control panel, DIP switch and antenna, adding the LoRa expanders in TrikdisConfig, indicator lights, frequently asked questions.
- 12 min read
1. Overview
The RF-LORA wireless transceiver (in TrikdisConfig: RF-LORA transceiver) is the central element of the Trikdis wireless family. With an RF-LORA connected to the FLEXi SP3 control panel, a wireless or a hybrid (mixed: wired and wireless) alarm system can be built. These wireless devices can be detectors, sirens, panic buttons, or inputs (zones) or controllable outputs (PGMs) on remote expander modules.
This manual describes the 4F (433 MHz) version; it does not cover the 8F (868 MHz) versions.
Together with the iO-LORA and iO8-LORA wireless expanders, the RF-LORA increases the number of inputs and outputs of the FLEXi SP3 over a two-way radio link. It connects to the alarm control panel by wire, on the RS485 bus, and with a clear line of sight it offers a wireless range of up to 5000 metres.
The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.
1.1 What does it work with?
The RF-LORA is compatible with the FLEXi SP3 alarm control panel, as well as with the GATOR (GV17, cellular) and the GATOR WiFi (WP17) gate and door controllers. One RF-LORA can be connected to a FLEXi SP3.
Compatible devices with RF-LORA
- IO8-LORA - wireless expander with 8 contact (all contact can be chosen as input or output)
- IO-LORA - wireless expander with built in relay (mostly used for gates, doors, barriers, garage doors)
- PB-LORA - wireless panic button (use up to 250 panic buttons in one system )
- M4-MAG - wireless magnetic door contact
- M4-PIR - wireless Indoor PIR
- M4-SMK - wireless smoke detector
- M4-SIREN - wireless outdoor siren
- M4-EXTENDER - wireless signal repeater (range extender)
How many devices can connect to one RF-LORA:
- FLEXi SP3: up to 8 LoRa modules (iO-LORA, iO8-LORA, PB-LORA), with firmware of any receiver code (SP3_xxx0, xxx1, xxx2 or xxx4).
- FLEXi SP3, PB-LORA panic buttons: if the panel runs "release 2" firmware, version 1.16 or newer (for example SP3_xxx2_0116.fw), 250 panic buttons can be enrolled. With SP3_xxx4 firmware, up to 8 panic buttons can be used.
- FLEXi SP3, Maximum (M4) devices: up to 32 detectors, 16 sirens and 32 remote controls, with firmware of receiver code 4, version 1.21 or newer (SP3_xxx4; use the latest version) – see sections 1.7 and 6.6 of the FLEXi SP3 manual.
- GV17 GATOR: up to 8 iO-LORA units, plus one iO8-LORA (or one wired iO8 instead).
- WP17 GATOR WiFi: up to 8 iO-LORA units, with WP17 firmware 1.21 or newer.
With the FLEXi SP3, you add the LoRa expanders in the panel's TrikdisConfig settings (chapter 3). With the GATOR gate controller, you add the expanders in the gate controller's Modules list; the RF-LORA itself does not need to be added to the list there – see section 5.4.1 of the GV17 manual and section 5.4 of the WP17 manual.
1.2 Technical data
| Parameter | Value |
|---|---|
| Frequency | 433.3–434.7 MHz (4F version) |
| Modulation | LoRa |
| Supply voltage | 9–26 V DC |
| Current consumption | up to 50 mA in standby · up to 150 mA briefly, while transmitting |
| Message encryption | yes |
| Range in open space | up to 5000 m |
| Connection to the host device | RS485 bus |
| Operating environment | −20 °C … +50 °C, relative humidity up to 80% (at +20 °C) |
| Dimensions | 62 × 82 × 25 mm |
| Weight | 80 g |
The product comes with a standard antenna that suits most applications. If a good-quality link is needed over the greatest possible distance, use a higher-gain antenna (AX-ANT-KIT). It is also available in the shop:
RF-LORA large Antenna Meteor 433MHz
1.3 Parts
The controls and connectors of the RF-LORA on the case and on the printed circuit board:

- 1 SMA connector for the radio antenna
- 2 indicator lights (DATA/TROUBLE, POWER)
- 3 opening slot of the cover
- 4 terminal block for the external connections
- 5 USB Mini-B connector for updating the firmware
- 6 SW DIP switch
- 7 DJ1 button – switches the learning (pairing) mode of the LoRa modules on and off
The two switches of the SW DIP switch:
- Switch 1 – radio channel: OFF = RF1, ON = RF2. Change it if the current channel is heavily loaded.
- Switch 2 – modulation: OFF = fast, ON = slow. In the ON position the range roughly doubles, depending on the environment; if the link is also good in the OFF position, use that.
In the ON position (slow modulation) the system reacts more slowly, and the battery of the PB-LORA panic button runs down sooner.
The switch positions must match
The SW switches of the RF-LORA and of all the LoRa modules connected to it must be in the same position, otherwise there is no radio link.
1.4 Terminals
| Terminal | Function |
|---|---|
| +DC | supply voltage, positive (9–26 V DC) |
| −DC | supply voltage, negative |
| A 485 | RS485 bus, A |
| B 485 | RS485 bus, B |
| IO1–IO4 | not used |
| COM | not used |
Attention!
The 4 I/O terminals on the device (IO1–IO4) and the COM terminals cannot be used.
1.5 Indicator lights
| Indicator | State | Meaning |
|---|---|---|
| DATA/TROUBLE | flashes or lights red | the connection with the module has been lost |
| DATA/TROUBLE | flashes green and red | learning mode: pairing the LoRa modules |
| DATA/TROUBLE | lights green for 3 seconds | in learning mode: a LoRa module has been paired |
| POWER | off | no supply voltage |
| POWER | flashes green | normal supply voltage |
| POWER | flashes yellow | low supply voltage (11.5 V or less) |
| POWER | lights yellow | no RS485 connection with the FLEXi SP3 |
2. Mounting and wiring
Warining!
It is forbidden to perform wiring on a device under voltage. Before starting the work, disconnect power (including backup batteries).2.1 Mounting
- Remove the cover.
- Take out the printed circuit board.
- Fix the bottom of the case in the desired place with screws.
- Put the board back.
- Close the cover.


2.2 Connecting to the FLEXi SP3
Connect the RF-LORA to the RS485 bus of the FLEXi SP3; it also takes its power from the panel's AUX output:
| FLEXi SP3 | RF-LORA |
|---|---|
| AUX+ (+12 V) | +DC |
| AUX− | −DC |
| 485 A | A 485 |
| 485 B | B 485 |

- W wireless link ("Wireless connection"), up to 5000 m ("up to 5000 m")
The “up to … m” distances are theoretical maximums achievable under ideal conditions. In practice, the quality and routing of the cable, sources of interference and, for radio links, walls and terrain give a considerably shorter range. Plan with a margin, and on long runs check the connection during commissioning.
The LoRa modules do not need to be wired to the panel: each gets its power at its own location – the iO-LORA and the iO8-LORA from a power supply, the PB-LORA panic button from a battery – and connects to the RF-LORA by radio. The wiring of the modules is described in their own manuals.
3. Setup in TrikdisConfig
You add and set up the LoRa expanders in the TrikdisConfig settings of the FLEXi SP3.
All Trikdis devices can be programmed using a common software. The software is called TrikdisConfig and can be downloaded from the manufacturer's website.
After downloading, install the program. If a new version is available each time you start TrikdisConfig, download and install the recommended update!
- The RF-LORA must be connected to the FLEXi SP3 (2.2).
- Switch on the supply voltage of the FLEXi SP3.
- Switch on the power of the iO-LORA or iO8-LORA expanders.
- Start TrikdisConfig.
- Connect the FLEXi SP3 to the computer with a USB Mini-B cable, or connect to it remotely.
- Press the Read [F4] button: the program reads the panel's settings. If the program asks for it, enter the six-character administrator code.
- In the Modules list, select the iO-LORA expander or the iO8-LORA expander item.
- In the Serial No. field, enter the serial number of the module.
- On the Zones tab, set up the expander's inputs: in the zone's Input list, the expander's inputs appear under the name RS485 Expander ID….
- On the PGM tab, set up the expander's outputs in the same way, in the PGM output list.
- At the end of the setup, press the Write [F5] button and wait until writing is finished.
- Press the Disconnect button and unplug the USB cable.
- Test the expander: trigger the inputs and switch the outputs.



Warning
While the device is connected to a computer via USB cable, it is in programming mode: its normal operation stops, it does not monitor, does not report, cannot be controlled, is powered from USB, and restarts once the cable is unplugged. Therefore the device must not be freely accessible: keep it in a closed metal enclosure with tamper protection or with a motion detector covering the enclosure. More in the FAQ
3.1 Registering the RF-LORA, enrolment
If the system also has Maximum (M4) wireless detectors, sirens, remote controls, or PB-LORA panic buttons in the 250-panic-button mode, the RF-LORA itself must also be added to the Modules → RS485 modules list (RF-LORA transceiver, with its serial number), and then the devices must be enrolled in learning mode in the Wireless sensors window. The steps are described in section 6.6 of the "FLEXi" SP3 alarm control panel – installation and programming manual.
- Learning mode is started by the Learn sensors button in TrikdisConfig or by the DJ1 button of the RF-LORA (in the FLEXi SP3 manual: LEARN); the DATA/TROUBLE light then flashes green and red.
- During enrolment, the RF-LORA should be at least 1 m away from the devices being enrolled.
4. Frequently asked questions
There is no radio link with the module – what should I check?
- Whether both switches of the SW DIP switch are in the same position on the RF-LORA and on the module (1.3) – with different positions there is no radio link.
- Whether the module has power, and whether its serial number in the Modules list is correct (chapter 3).
- The radio signal level is shown by the expander's NETWORK light with green flashes (0–10); 4 is already enough for the iO-LORA and 3 for the iO8-LORA, and the PB-LORA is recommended to be used with at least four flashes.
- With a weak signal, set switch 2 to ON (slow modulation) on every device, or use a higher-gain antenna (1.2).
The POWER light is steady yellow
The RF-LORA is not communicating with the FLEXi SP3 on the RS485 bus: check the A 485 and B 485 wires (2.2).
The POWER light flashes yellow
The supply voltage is low (11.5 V or less): check the power supply – the RF-LORA works from 9–26 V DC.
What are the IO1–IO4 and COM terminals for?
They cannot be used on the RF-LORA (1.4).
Which switch position should I choose?
By default, fast modulation (switch 2 OFF). If there is no reliable link because of the distance, slow modulation (ON) roughly doubles the range, depending on the environment, but the system reacts more slowly. Change the channel (switch 1) if the current channel is heavily loaded. Whichever you change, set it the same way on every LoRa device.
5. Safety instructions
Attention!
Electricity can be dangerous and may cause personal injury or DEATH, as well as other financial loss or damage if not used or installed properly.
Installation involves working with electrical equipment, and it should be executed in accordance with current regulations!
Warranty validation requires the device to be installed by a qualified person following the installation regulations for electrical equipment and adhering to the current regulations for the safe operation of electrical equipment.
- The RF-LORA may only be installed and maintained by qualified persons.
- Before installation, read this manual carefully to avoid mistakes that could lead to malfunction or even damage to the equipment.
- Disconnect the power before making any connection.
- Changes, modifications or repairs not authorized by the manufacturer void the warranty.
- Do not throw the device and its parts in household waste: follow the local waste sorting regulations.
See also
- "FLEXi" SP3 alarm control panel – installation and programming manual – wiring and setting up the panel, including registering the RF-LORA and enrolling the wireless devices (6.6).
- GV17 GATOR gate controller – installation and programming manual and WP17 GATOR WiFi gate controller – installation and programming manual – adding the LoRa expanders in the gate controller's Modules list.
- Flexible wireless access control with the GATOR RF-LoRa system – several gates wirelessly with one GATOR.
- The LoRa modules in the shop:
Trikdis IO-LORA wireless expander module
Trikdis IO8-LORA wireless expander module
Trikdis PB-LORA wireless panic button
- Trikdis documentation: docs.trikdis.com – RF-LoRa Wireless Expander.